IDEAL 800 Series Manual Download Page 9

18

17

• Connect the black test probe to ground and the red test

probe to the second phase (T or L2).

• Using the trigger to open the jaws, fully enclose the phase

(T or L2) within the clamp.  

• Release the trigger and be sure that the jaws have closed

completely.

• Wait until the reading is stable, and press the READ NEXT

button to capture the reading, storing the data in memory.

• The power clamp processes the two sets of data and calcu-

lates the true power (kW) of the system, which is shown on
the main display, and the power factor (PF), which is shown
on the upper display.  RST is shown on the LCD display to
indicate that this is a measurement of the total system.

• Pressing the 3

φ

KVAR KVA button toggles to display the

apparent power (kVA) of the system, which is shown on the
main display, and the reactive power (kVAR), which is
shown on the upper display.

• Pressing the READ NEXT button clears the stored data from

memory and readies the power clamp for another single
phase 3-wire calculation.

3

φ

4W AC+DC Power Measurements

Kilowatt Range

Voltage/Current

(AC+DC True Power) Resolution Accuracy

Range  

0-99.99kW 

0.01kW 

±(2.0% +0.05)  600VAC, 800VDC

100-999.9kW 

0.1kW

2000A AC/DC      

1000-1200kW 

1kW 

±(2.0% +5)   

Power Factor 0.2-1.0 for 1

φ

2W, 1

φ

3W, 3

φ

3W, and 3

φ

4W 

In a three phase 4-wire system, the 61-802 power clamp mea-
sures the true power (kW), power factor (PF), apparent power
(kVA), and reactive power (kVAR) of the system.  These values
are calculated based on the formulas

kW

3

φ

4W

= kW

3

φ

4W

= kW

R(L1)

+ kW

S(L2)

+ kW

T(L3)

PF

3

φ

4W

=

kVA

3

φ

4W

=

kVAR

3

φ

4W

= kVAR

R(L1)

+ kVAR

S(L2)

+ kVAR

(TL3)

To Measure AC+DC Power Measurements in a three
phase 4-wire system 

• Set rotary switch to 3

φ

4W without jaws clamping onto any

wire.

• The LCD display will show a flashing R to indicate that the

meter is ready for the first measurement.

• If the watt reading is not zero, press the DC A/W ZERO but-

ton once to zero out the watt reading.

• Insert the black test lead into the COM terminal and the red

test lead into the + terminal.

kW 3

φ

4W

kVA 3

φ

4W

kW

2

3

φ

4W

+ kVAR

2

3

φ

4W

Summary of Contents for 800 Series

Page 1: ...61 802 2 61 802 800 Series Power Clamp Meter 3 PF AC DC 2000KW 2000A OFF PFKW HzV 3 3W 3 4W KVARKVA VA DC A W ZERO REC 3 KVAR KVA READ NEXT HOLD CAT III 600V Power Clamp True RMS 61 802 1 Transformer...

Page 2: ...fingers behind the finger guards on the probes Work with others 6 Before beginning all unknown measurements set meter to highest possible range 7 Before breaking a circuit for testing turn off the po...

Page 3: ...4W system After these values have been calculated press the 3 KVAR KVA button to display the KVAR and KVA values for the sys tem To start another calculation press the read next button again to return...

Page 4: ...PF indicates an inductive load while negative PF indicates a capacitive load 8 To measure Kilowatts and Power Factor in a single phase 3 wire system See section on 1 3W AC DC Power Measurements AC DC...

Page 5: ...e the trigger and be sure that the jaws have closed completely Insert the black test lead into the COM terminal and the red test lead into the terminal Connect the test probes in parallel with the loa...

Page 6: ...AC DC Power Measurements 3 3W AC DC Power Measurements Kilowatt Range Resolution Accuracy Voltage Current AC DC True Power Range 0 99 99kW 0 01kW 2 0 0 05 600VAC 800VDC 100 999 9kW 0 1kW 2000A AC DC 1...

Page 7: ...third phase eg T or L3 Using the trigger to open the jaws fully enclose the phase T or L3 within the clamp Release the trigger and be sure that the jaws have closed completely Wait until the reading...

Page 8: ...W ZERO but ton once to zero out the watt reading Insert the black test lead into the COM terminal and the red test lead into the terminal 16 L1G Measurement Connect the black test probe to ground and...

Page 9: ...data from memory and readies the power clamp for another single phase 3 wire calculation 3 4W AC DC Power Measurements Kilowatt Range Voltage Current AC DC True Power Resolution Accuracy Range 0 99 9...

Page 10: ...ess the READ NEXT button to capture the reading storing the data in memory The LCD display will show a flashing T to indicate that the meter is ready for the next measurement Remove the clamp and test...

Page 11: ...e used in a 1 2W or 3 4W systems Three phase capacitors are available for 3 3W and 3 4W systems Determining the Required Capacitor Value Measure the kVAR3 3W value of the power system The capacitor va...

Page 12: ...Lifetime Limited Warranty This meter is warranted to the original purchaser against defects in material or workmanship for the lifetime of the meter During this warranty period IDEAL INDUSTRIES INC wi...

Reviews: