IDEAL 800 Series Manual Download Page 4

To measure Kilowatts and Power Factor in a single
phase 2-wire system

• Set rotary switch to PF/kW without jaws clamping onto any

wire

• If the watt reading is not zero, press the DC A/W ZERO 

button once to zero out the watt reading.

• Insert the black test lead into the COM terminal and the red

test lead into the + terminal.

• Connect the black test probe to the neutral conductor and

the red test probe to the hot conductor.

• Using the trigger to open the jaws, fully enclose the hot

conductor within the clamp.

• Release the trigger and be sure that the jaws have closed

completely.

• The power clamp selects the appropriate range based on the

Autoranging table.

• Power Factor (PF) is a calculated value based on the 

formula

PF=

_______

• The kW value is shown on the main display and the PF

value is shown on the upper display.

• Positive PF (+) indicates an inductive load, while negative

PF (-) indicates a capacitive load.

8

To measure Kilowatts and Power Factor in a single
phase 3-wire system 

See section on 1

φ

3W AC+DC Power Measurements

AC+DC Voltage/Frequency Measurements

Voltage Resolution 

Accuracy

Accuracy

Input

Range (50/60Hz) 

(40-400Hz) Impedance

0-200V 

0.1V 

±(1.5% +5)  ±(2.0% +5)  10M

200-500V      

500-600VAC 1V

500-800VDC      

Overload Protection:

800V

TRMS Measurements 
Accuracies specified at Crest Factor <3.5

Frequency Range 

Accuracy 

Sensitivity  

50/60Hz 

±(0.5% + 2) 

>5V  

10-400Hz    

To Measure Voltage and Frequency

• Set the rotary switch to V/Hz
• Insert the black test lead into the COM terminal and the red

test lead into the + terminal.

• Connect the test probes in parallel with the load or circuit.
• The power clamps automatically selects the proper range.

Note:  The “+” sign on the jaw must face the power source for
correct measurement.

kW

kVA

3ØPF
AC+DC
2000KW
2000A

OFF

PFKW

HzV

3Ø3W

3Ø4W

KVARKVA

VA

DC
A/W
ZERO

REC

3

Ø

KVAR
KVA

READ
NEXT

HOLD

CAT III - 600V

Power Clamp

True RMS

61-802

7

Summary of Contents for 800 Series

Page 1: ...61 802 2 61 802 800 Series Power Clamp Meter 3 PF AC DC 2000KW 2000A OFF PFKW HzV 3 3W 3 4W KVARKVA VA DC A W ZERO REC 3 KVAR KVA READ NEXT HOLD CAT III 600V Power Clamp True RMS 61 802 1 Transformer...

Page 2: ...fingers behind the finger guards on the probes Work with others 6 Before beginning all unknown measurements set meter to highest possible range 7 Before breaking a circuit for testing turn off the po...

Page 3: ...4W system After these values have been calculated press the 3 KVAR KVA button to display the KVAR and KVA values for the sys tem To start another calculation press the read next button again to return...

Page 4: ...PF indicates an inductive load while negative PF indicates a capacitive load 8 To measure Kilowatts and Power Factor in a single phase 3 wire system See section on 1 3W AC DC Power Measurements AC DC...

Page 5: ...e the trigger and be sure that the jaws have closed completely Insert the black test lead into the COM terminal and the red test lead into the terminal Connect the test probes in parallel with the loa...

Page 6: ...AC DC Power Measurements 3 3W AC DC Power Measurements Kilowatt Range Resolution Accuracy Voltage Current AC DC True Power Range 0 99 99kW 0 01kW 2 0 0 05 600VAC 800VDC 100 999 9kW 0 1kW 2000A AC DC 1...

Page 7: ...third phase eg T or L3 Using the trigger to open the jaws fully enclose the phase T or L3 within the clamp Release the trigger and be sure that the jaws have closed completely Wait until the reading...

Page 8: ...W ZERO but ton once to zero out the watt reading Insert the black test lead into the COM terminal and the red test lead into the terminal 16 L1G Measurement Connect the black test probe to ground and...

Page 9: ...data from memory and readies the power clamp for another single phase 3 wire calculation 3 4W AC DC Power Measurements Kilowatt Range Voltage Current AC DC True Power Resolution Accuracy Range 0 99 9...

Page 10: ...ess the READ NEXT button to capture the reading storing the data in memory The LCD display will show a flashing T to indicate that the meter is ready for the next measurement Remove the clamp and test...

Page 11: ...e used in a 1 2W or 3 4W systems Three phase capacitors are available for 3 3W and 3 4W systems Determining the Required Capacitor Value Measure the kVAR3 3W value of the power system The capacitor va...

Page 12: ...Lifetime Limited Warranty This meter is warranted to the original purchaser against defects in material or workmanship for the lifetime of the meter During this warranty period IDEAL INDUSTRIES INC wi...

Reviews: