Ideal Heating IMAX XTRA 2 Manual Download Page 6

6

Conversion Kit

RE-LOADING THE NATURAL GAS PARAMETERS

MENU

Switched Live Control

Burner Stabilisation

Heating

Hot Water

ACTUAL

TARGET

75°

75°

ACTUAL

TARGET

75°

75°

Demand On

No Demand

100%

NEXT

No

Yes

Boiler Conversion

Gas Type

NEXT

NEXT

NEXT

Natural Gas ANZ

LPG

Natural Gas

Menu

Status

Settings

Configuration

Service

Access Level

View Config

Flow Temperature

Boiler Conversion

Factory Reset

Configuration

NEXT

No

Yes

Restore Current Configuration

PROCEED

CANCEL

Performing this action will reconfigure

using current configuration settings.

Are you sure?

NEXT

Boiler Power

80kW

Gas Type
Boiler Power
Set

NG
80kW
11

Gas Type

NEXT

NEXT

CONFIRM

Yes

Yes

Config

User Menu

Select the boiler type then press NEXT

Boiler Conversion

Select the boiler size from the list using 

the up/down arrows then press SELECT

Proceed

MENU

CONFIRM

1.  Refer to safety section.

2.  Enter service mode using access code 529. Please refer to 

the Installation & Servicing manual for further information   

on this.

3.  Follow the steps below to upload the parameters for Natural 

Gas.

Steps to follow for boiler that has been previously configured as an LPG boiler

Summary of Contents for IMAX XTRA 2

Page 1: ...nditioned or copy parts that have not been clearly authorised by Ideal Heating For the very latest copy of literature for specification and maintenance practices visit our website idealheating com whe...

Page 2: ...ailure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to ensure the law is complied with kW NG Product No Imax Xtra 2 80 225464 Imax Xtra 2 120...

Page 3: ...682118 80kWIMAXXTRA2 RECORDTHE ORIGINALBOILER DETAILS BOILERTO BE INSTALLED GAS SUPPLY PRESSURE 20mbar IMPORTANT After completing the servicing or replacement of components always Test for gas soundne...

Page 4: ...s and remove Front Panel 3 Remove the 3 bolts along the top of the front panel The bolts are visible when the control pod is removed Pull the panel forwards at the top lift out of bottom slot and remo...

Page 5: ...re it is secure 3 Replace the four bolts that have been removed with the four new M5 x 12mm bolts supplied in the conversion kit Ensure an even tightening sequence of the bolts REMOVING THE ORIFICE PL...

Page 6: ...L Performing this action will reconfigure using current configuration settings Are you sure NEXT Boiler Power 80kW Gas Type Boiler Power Set NG 80kW 11 Gas Type NEXT NEXT CONFIRM Yes Yes Config User M...

Page 7: ...rate without modulating set the fan speed to minimum following the steps in the gas valve adjustment diagram on the next page 5 Using the minimum rate adjustment screw adjust the valve until the CO2...

Page 8: ...ure Return Temperature Flame Current 6800 rpm 6800 rpm 10 Minutes 75 c 60 c 5 7 A MAX RATE To set the boiler to run at Maximum Rate for 10 Minutes press Maximum Rate The boiler will run at Maximum Rat...

Page 9: ...the two tear off strips 4 Once all details have been recorded adhere one of the two tear off strips over the existing label at the rear of the boiler and the other one over the existing label on the...

Page 10: ...Conversion Kit 10 NOTES...

Page 11: ...Conversion Kit 11 NOTES...

Page 12: ...Heating we take our environmental impact seriously therefore when installing any Ideal Heating product please make sure to dispose of any previous appliance in an environmentally conscious manner Hous...

Reviews: