38
Installation and Servicing
SECTION 3 - SERVICING
5
7
1.
Isolate and drain the HIU. Refer to Section 3.5.
2.
Remove the front panel. Refer to Section 3.4.
3.
Remove insulation front section to expose plate heat
exchanger(s). Refer to Section 3.12.
4.
Slacken the four pipe nuts on the front face of the RHS
plate. Ensure support is used to not twist the elbow
manifolds. Dispose of fibre washers to prevent re-use.
5.
Remove the four screws securing the two plate heat
exchanger brackets (upper and lower) to the chassis.
6.
Manoeuvre the plate heat exchanger out of the appliance.
Be aware of any water spillage.
7.
Remove the clips from the plate heat exchanger by pulling
the upper one downward and the lower one upward. Lightly
twist and pull the elbows to remove them from the O-ring
seals on the PHE.
8.
Fit new blue O-ring seals to the upper most groove on the
4 PHE connection posts. (the low groove nearest the PHE
is for the retention clip).
9.
Ensure the two indents near the PHE connection posts are
facing inboard.
10.
Refit the two 90° elbows to the top of the PHE with their
outlets facing left and right, and the 2 x 60° elbows are
fitted with their outlet facing downwards.
Note:
Failure to correctly locate the poisition of the elbows
will prevent the retention clips from being fitted.
11.
Ensure new retention clips are located correctly in the
slots on the brass elbows and that they are secured to
the correct groove on the PHE connect post.
Note:
If they
are not correctly fitted the groove nearest the PHE will be
clearly visible. In this case the clip will need to be removed
and the elbows pushed further on the PHE connection
posts and the clip refitted.
12.
Fit the new plate heat exchanger into the cut out in
insulation back panel – ensure CH plate size is matched to
plate removed.
Note:
Ensure that the depressions on the plate heat
exchanger are facing inboard and match the insulation.
13.
Refit the four screws securing the upper and lower bracket
to the chassis, including the upper manifold bracket.
14.
Replace fibre washers with new (supplied) and spin nuts
onto manifold threads.
15.
Torque the 90 degree manifold (TOP) pipe nut connections
to 40N/m.
16.
Torque the 60 degree manifold (BOTTOM) pipe nut
connections to 32N/m.
17.
Refill the HIU. Refer to Section 2.5.
18.
Replace the insulation front section. Refer to Section 3.12.
19.
Check that the HIU operates in both DHW & CH modes.
3.14 CH PLATE HEAT EXCHANGER REMOVAL & REPLACEMENT
SER
VICING