background image

10

 

Installation and Servicing

SECTION 1 - GENERAL

1.1 INTRODUCTION

The

 i-mini C 

range of boilers are wall mounted, full sequence, 

automatic spark ignition, low water content, fanned flue, high 

efficiency, condensing, combination gas boilers.

Note. 

Due to the high efficiency of the boiler a plume of water 

vapour will form at the terminal during operation.

Central heating (CH) output is fully modulating with a range of:
24 

4.8 to 24.2kW

30 

6.1 to 24.2kW

Instantaneous domestic hot water (DHW) output is also fully 

modulating with a maximum of :
24 24.2kW
30 30.3kW
The boiler is supplied fully assembled with DHW plate heat 

exchanger, diverter valve, circulating pump, pressure gauge, 

safety valve and CH expansion vessel.

Variable CH and DHW temperature controls are fitted on the user 

control and the boiler features a DHW preheat facility.
The boiler includes as standard:

Automatic bypass

Boiler frost protection

Daily pump and diverter valve exercise

The boiler casing is of white painted mild steel with a white 

polymer front panel.
The boiler temperature controls are visible located in the control 

panel on the front of the boiler.
The heat exchanger is manufactured from cast aluminium.
The boiler is suitable for connection to fully pumped, sealed 

heating systems ONLY.  Adequate arrangements for completely 

draining the system by provision of drain cocks MUST be provided 

in the installation pipework.
Pipework from the boiler is routed downwards.

Data Plate

The boiler model and serial number can be located on the bottom of the 

boiler casing, shown in Frame 1 - Water & Gas Connection Diagram.

1.2 OPERATION

With no demand for CH, the boiler fires only when DHW is drawn 

off, or periodically for a few seconds without any DHW draw-off, in 

order to maintain the DHW calorifier in a heated condition.  This 

only occurs if pre-heat knob is in the ‘ON’ period.
When there is a demand for CH, the heating system is supplied at 

the selected temperature of between 30

o

C and 80

o

C, until DHW 

is drawn off.  The full output from the boiler is then directed via 

the diverter valve to the plate heat exchanger to supply a nominal 

DHW draw-off of 
24 

9.9 l/min at 35 

o

C temperature rise.

30 

12.4 l/min at 35 

o

C temperature rise.

The DHW draw off rate specified above is the nominal that the 

boiler flow regulator will give.  Due to system variations and 

seasonal temperature fluctuations DHW flow rates/temperature 

rise will vary, requiring adjustment at the draw off tap.
At low DHW draw-off rate the maximum temperature may exceed 

65ºC. 
The boiler features a comprehensive diagnostic system which 

gives detailed information on the boiler status when operating, 

and performance of key components to aid commissioning and 

fault finding.

1.3  SAFE HANDLING

This boiler may require 2 or more operatives to move it to its 

installation site, remove it from its packaging base and during 

movement into its installation location.  Manoeuvring the boiler 

may include the use of a sack truck and involve lifting, pushing and 

pulling.  
Caution should be exercised during these operations.
Operatives should be knowledgeable in handling techniques when 

performing these tasks and the following precautions should be 

considered:
•  Grip the boiler at the base.

•  Be physically capable.

•  Use personal protective equipment as appropriate, e.g. gloves, 

safety footwear.

During all manoeuvres and handling actions, every attempt should 

be made to ensure the following unless unavoidable  and/or the 

weight is light.
•  Keep back straight.

•  Avoid twisting at the waist.

•  Avoid upper body/top heavy bending.

•  Always grip with the palm of the hand.

•  Use designated hand holds.

•  Keep load as close to the body as possible.
•  Always use assistance if required.

1.4  OPTIONAL EXTRA KITS

•  Telescopic Horizontal Flue Terminal  (1000mm long)
•  Telescopic Horizontal Flue Terminal (600mm long)
•  Telescopic Horizontal B Pack Flue (600mm long) 

•  Flue Extension Ducts  (1000mm long)

•  Flue Extension Ducts  (2000mm long)

•  Flue Extension Ducts  (500mm long) 

24-up to 9m 

30-up to 8m

• 90

o

 Elbow Kit (maximum per installation). 

24-upto 6 elbows 

30-upto 6 elbows

• 45

o

 Elbow Kit (maximum per installation). 

24-upto 6 elbows 

30-upto 6 elbows

•  Roof Flue Kit (inc. vertical connector) (to a maximum of 7.5m)
•  Flue Finishing Kit
•  High Level Flue Outlet Kit
•  Balcony Flue Kit

•  Soffit Flue Kit

•  Adjustable Flue Support Bracket

•  Flue Deflector Kit
•  Raised Horizontal Flue Outlet Kit

•  Concentric Flue Screw Retaining Kit
•  Weather Collar
•  Stand-Off Kit
•  Condensate Pump Kit
•  DHW Expansion Vessel Kit
•  Weather Compensation Kit
•  PRV Wall Outlet Kit
•  Security Bracket Kit
•  Mechanical Timer (24hr) Kit

Summary of Contents for i-mini C24

Page 1: ...t you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy...

Page 2: ...W 24 3 24 3 Part Load P1 kW 8 0 8 0 Auxiliary Electricity Consumption Full Load elmax kW 0 042 0 032 Part Load elmin kW 0 012 0 013 Standby PSB kW 0 005 0 005 Seasonal Space Heating Energy Efficiency...

Page 3: ...I Class VIII 1 2 1 5 2 3 4 3 5 5 PRODUCT FICHE The energy efficiency of the package of products provided for in this document may not correspond to its actual energy efficiency once installed in a bui...

Page 4: ...4 Installation and Servicing...

Page 5: ...19 Ideal Boilers reserve the right to vary specification without notice FOR ANY TECHNICAL QUERIES PLEASE RING THE IDEAL INSTALLER HELPLINE 08708 498057 NOTE BOILER RESTART PROCEDURE To restart the bo...

Page 6: ...6 Installation and Servicing...

Page 7: ...ement 40 3 3 Fan And Venturi Assembly Removal And Cleaning 40 3 4 Burner Removal And Cleaning 41 3 5 Cleaning The Condensate Trap Siphon 41 3 6 Cleaning The Heat Exchanger 42 3 7 Reassembly 42 3 8 Rep...

Page 8: ...h divide the gross heat input Btu h by the gross C V of the gas Btu ft3 d For m3 h multiply l s by 3 6 Key to symbols GB United Kingdom IE Ireland Countries of destination PMS Maximum operating press...

Page 9: ...reducer 16 Hot water mode Heat input to be calculated Max operating burner pressure n a Max operating water pressure measure record Cold water inlet temp measure record Hot water outlet temp measure...

Page 10: ...in at 35 o C temperature rise The DHW draw off rate specified above is the nominal that the boiler flow regulator will give Due to system variations and seasonal temperature fluctuations DHW flow rate...

Page 11: ...device not approved by Ideal Boilers could invalidate the certification and the normal appliance warranty It could also infringe the Gas Safety Regulations and the above regulations 1 6 SAFE HANDLING...

Page 12: ...tion otherwise BS5440 1 2008 dimensions must be followed Flue Terminal Positions Min Spacing 1 Directly below above or alongside an opening window air vent or other ventilation opening 300mm 12 2 Belo...

Page 13: ...radiator valves are used the space heating temperature control over a living dining area or hallway having a heating requirement of at least 10 of the minimum boiler heat output should be achieved us...

Page 14: ...ill the flue can be installed from inside the building where wall thicknesses do not exceed 600mm Where the space into which the boiler is going to be installed is less than the length of flue require...

Page 15: ...r capacity of the system should not exceed 143 litres if not pressurized However if the system is to be pressurized the efficiency of the expansion vessel will be reduced and a larger vessel or smalle...

Page 16: ...al water company The use of artificially softened water however is not permitted Ideal Boilers recommend the use of Fernox Quantomat Sentinel Combiguard and Calmag CalPhos I scale reducing devices whi...

Page 17: ...Assy 214 Venturi 215 Fan 217 Burner 218 Gasket Burner 219 Sump Clean Out Cover 223 Flue Manifold 224 Flue Manifold Top 227 Clamp Retaining Flue Turret 228 Hose Condensate Internal 229 Siphon Trap 231...

Page 18: ...11 8 9 2 6 5 1 12 2 2 UNPACKING The boiler is supplied fully assembled in Pack A A telescopic or non telescopic flue assembly for rear or side flue outlet in Pack B is suppled as a separate order Unpa...

Page 19: ...let nose that utilises a push fit location system This enables the installation of deflector high level or balcony outlet flue kits without the removal of the whole B pack terminal The appliance must...

Page 20: ...NT Ensure that during the cutting operation masonry falling outside of the building does not cause damage or personal injury 1 Cut the flue hole preferably with a 5 core boring tool ensuring that the...

Page 21: ...aps seals are in place Additional Termination Kits available for use with these B packs Flue Deflector Kit The resistance is the equivalent of 1 metre of flue pipe and therefore must be deducted from...

Page 22: ...ue Terminal 1000mm long B Pack Telescopic Cut 75mm Minimum Maximum Minimum Maximum Minimum Maximum Minimum Maximum B Pack Standard 181 556 286 484 601 816 526 741 Plus 1 1m D pack 1121 1506 1236 1434...

Page 23: ...he outlet terminal is upper most 4 Drill a 3 5mm hole through one of the 2 outer side holes in the outer flue section into the inserted outer flue as shown Take care not to pierce the inner plastic fl...

Page 24: ...been dislodged from its mounting and will need to be refitted 7 Ensure the seam and the outlet terminal are at the top and fitted as shown Note If less than 50 of the length of the flue is internal t...

Page 25: ...the boiler is made using the supplied vertical connector WEATHER PROOFING Where the flue passes through the roof line an adequate seal must be made This is achieved by using either Flat roof weather c...

Page 26: ...tructions provided with the vertical connector kit 3 Secure the vertical connector by applying downward pressure on the connector 4 Position the clamp on the top face of the flue manifold and push it...

Page 27: ...enetrate the shaded area of the roof Note The equivalent flue length resistance of the elbow kits are 90o elbow kit 1m 45o elbow kit 0 6m If chimney penetrates dotted area such that A is less than 300...

Page 28: ...nal soil and vent stack or internal kitchen or bathroom waste pipe etc fig 3 External Drain Connections The use of an externally run condensate drainage pipe should only be considered after exhausting...

Page 29: ...pipe Water Weather proof insulation Max 3m external pipework Limestone chippings 500 300 25 2 rows of three 12mm holes 25mm centres 50mm from the bottom of the tube facing away from the house Minimum...

Page 30: ...the bottom right hand side of the boiler comprises a 15mm diameter stub pipe The discharge pipe should be positioned so that the discharge of water or steam cannot create a hazard to the occupants of...

Page 31: ...ny local regulations 2 18 INSTALLER WIRING A mains cable must be connected to a permanent live supply and NOT switched by thermostats programmers To do so follow the instructions below Accessing the i...

Page 32: ...DAMAGED Outside Sensor Open Therm OpenTherm Device E G Honeywell OT Bridge R8810 External Controls 230V 50Hz Wiring a 230V 50Hz Room Thermostat Diagram A with optional timer Diagram B 1 Remove the lin...

Page 33: ...2 PUMP LIVE DHW LIVE X3 PUMP GND X9 X8 OWC OWC OPENTHERM OPENTHERM OPENTHERM 5V CHIP COM BUS TX CHIP COM BUS 24V CHIP COM BUS GND CHIP COM BUS 5V CHIP COM BUS RX MAINS LIVE MAINS NEUTRAL AUXILIARY LIV...

Page 34: ...tion on the gas type defined on the appliance data plate DO NOT adjust the air gas ratio valve Having checked That the boiler has been installed in accordance with these instructions The integrity of...

Page 35: ...est point H and connect a gas pressure gauge via a flexible tube 8 Switch the electricity supply ON and check all external controls are calling for heat Note The boiler incorporates a fan overrun cycl...

Page 36: ...show then when the burner lights 2 Close all taps except the furthest one from the boiler and check that the boiler is firing at maximum rate This is factory set to give a DHW temperature rise of appr...

Page 37: ...PREHEAT 4 VF will be shown To activate the venting function press RESTART otherwise press PREHEAT The venting function runs for 5 minutes before automatically returning to normal operation The diverte...

Page 38: ...d the requirement to register it to receive the full benefit of the warranty 1 Hand the User Instructions to the householder and explain his her responsibilities under the relevant national regulation...

Page 39: ...use of electronic portable combustion gas analysers in accordance with BS7967 Parts 1 to 4 Flue Sampling Point Air Sample Point Ensure all caps and seals are re fitted after use Note In order to carry...

Page 40: ...e two M4 screws and release the nozzle assembly 6 Inspect the injector for blockage or damage 7 Inspect fan outlet sealing gasket and replace if necessary REMOVAL 1 Loosen the two screws retaining the...

Page 41: ...The burner head is a ceramic plaque construction Care must be taken to ensure that the burner is not placed down upon its face as this may cause damage to the ceramic 6 Brush off any deposits that ma...

Page 42: ...nition and detection gaps are correct Refer to Sections 3 13 3 14 1 Ignition Electrode Flame Detection Reassemble the boiler in the following order 1 Ensure that the condensate trap siphon is full of...

Page 43: ...boiler Refer to Section 3 21 THE BOILER MUST NOT BE OPERATED WITHOUT THE FRONT PANEL FITTED 3 9 FAN REPLACEMENT 1 Refer to Section 3 8 2 Disconnect the electrical leads from the fan 3 Remove the clip...

Page 44: ...rse order ensuring that the new gas seal supplied is located correctly in the injector housing 10 Check that the boiler operates in both DHW CH modes 4 3 3 3 11 BURNER REPLACEMENT 5 5 6 1 See Section...

Page 45: ...8 Reassemble in reverse order 9 Check the operation of the boiler Refer to Section 2 23 2 24 3 12 RETURN THERMISTOR REPLACEMENT 1 Refer to Section 3 8 2 Unclip the return thermistor from the return p...

Page 46: ...rode 4 Remove the 2 screws retaining the detection electrode 5 Remove the electrode 6 Fit the new flame detection electrode using the new gasket supplied 7 Reassemble in reverse order 8 Check that the...

Page 47: ...ewdriver in the actuator slot provided and ease out the actuator 3 Before replacing the diverter valve actuator proceed as follows a Ensure that the switched live to the boiler is off and that all DHW...

Page 48: ...ut the four side retaining clips and pull the PCB upwards to clear the corner retaining posts 7 Take the new PCB 8 Re connect all plug connections 9 Reassemble in reverse order 10 a Turn power on disp...

Page 49: ...ngth of hose to the CH drain point 4 After replacing any component on the boiler remove the hose close the drain valve and open all system isolating valves re pressurise as appropriate before proceedi...

Page 50: ...ction 3 32 4 Firstly increase access area by disconnecting the 22mm pipe connection at top of pump manifold and bottom of heat exchanger and remove pipe Refer to Section 3 26 5 The automatic air vent...

Page 51: ...y 1 Refer to Section 3 8 2 Drain the boiler Refer to Section 3 21 3 Remove the condensate trap siphon Refer to Section 3 18 4 Remove the electrical plug Refer to Section 3 17 5 Place a flat bladed scr...

Page 52: ...oiler Refer to Section 2 16 8 Check that the boiler operates in both DHW CH modes 3 30 FLOW THERMISTOR REPLACEMENT 4 3 3 29 CH WATER PRESSURE SWITCH REPLACEMENT 1 Refer to Section 3 8 2 Drain the boil...

Page 53: ...rectly match connecting pipe diameters 18 Ensure the trap siphon is filled with water Refer to Section 3 18 19 Refill the boiler and check for leaks Refer to Section 2 16 20 Ensure all gas valve conne...

Page 54: ...uit Refer to Section 3 21 8 Remove the retaining clip on the vessel water connection pipe and remove the pipe 9 Support the expansion vessel and unscrew the 2 screws from the securing bracket located...

Page 55: ...GO TO SECTION 4 9 RETURN THERMISTOR FAULT GO TO SECTION 4 10 OUTSIDE SENSOR FAULT LOW MAINS VOLTAGE CONTACT ELECTRICITY PROVIDER PCB UNCONFIGURED OR FAULTY SEE SECTION 3 19 IF FAULT PERSISTS REPLACE...

Page 56: ...rectify fault NO YES Is 24Vdc supply available at the Gas Valve YES Check spark generator and associated harness for continuity and visual condition Refer to Section 3 15 Are these functioning correct...

Page 57: ...these functioning correctly YES Check siphon and condensate drain pipe work for blockage and rectify if necessary Boiler now working OK Check wiring from gas valve to PCB for continuity If the wiring...

Page 58: ...1 000 1 100 Ohms Is the Thermistor value correct YES Is the wiring securely connected to the low voltage 6 way connector at the front left hand side of the PCB YES Replace PCB Fit a new Thermistor NO...

Page 59: ...and the PCB Replace PCB Fit a new Outside Sensor NO Securely connect the wiring at the Terminal Block and the PCB Is the wiring securely connected at both the boiler and Outside Sensor YES NO Securel...

Page 60: ...d the diverter valve motor connected YES YES Check diverter head fully engaged and clip secured onto waterset YES Is diverter stuck in the CH position YES Check and re fit diverter valve actuator head...

Page 61: ...ils of approved Ideal Parts Distributors are available on www idealparts com Our Parts team are also available to help with your Ideal Spare Parts enquiries on 01482 498665 When calling and to ensure...

Page 62: ...62 Installation and Servicing SECTION 5 SPARE PARTS...

Page 63: ...fields on the commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the b...

Page 64: ...priate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISSIONING CHECKLIST CONTROLS Programmable room thermostat Optimum start control Combinati...

Page 65: ...larly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND Signature SERVICE 02 AND Where Possible AND Signature SERVICE 03 A...

Page 66: ...ical Bulletin TB 008 where chimney flues are in voids The ECGA should be of the correct type as specified by BS 7967 Prior to its use the ECGA should have been maintained and calibrated as specified b...

Page 67: ...bled fixed and supported as per instructions Check that flue and flue terminal are not obstructed Check that no seals e g Those on flue extensions have been displaced during installation Rectify if ne...

Page 68: ...68 NOTES Installation and Servicing...

Page 69: ...69 NOTES Installation and Servicing...

Page 70: ...70 NOTES Installation and Servicing...

Page 71: ...71 NOTES Installation and Servicing...

Page 72: ...The code of practice for the installation commissioning servicing of central heating systems Ideal Installer Technical Helpline 0870 849 8057...

Reviews: