When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance 

specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Heating.
For the very latest copy of literature for specification and maintenance practices visit our website idealheating.com  

where you can download the relevant information in PDF format.

FLUE DAMPER KIT 

INSTALLATION

IMAX XTRA 2

80 120 160 200 240 280

80P 120P 160P 200P 240P

October 2021
UIN 230511 A01

Summary of Contents for EVOMAX 2 40

Page 1: ...ditioned or copy parts that have not been clearly authorised by Ideal Heating For the very latest copy of literature for specification and maintenance practices visit our website idealheating com where you can download the relevant information in PDF format FLUE DAMPER KIT INSTALLATION IMAX XTRA 2 80 120 160 200 240 280 80P 120P 160P 200P 240P October 2021 UIN 230511 A01 ...

Page 2: ...arts 1 Motorised flue damper Shown in Fig 1 1 2 FLUE DAMPER KIT PARTS 1 3 INSTALLING THE MOTORISED FLUE DAMPER INTO THE FLUE Fig 1 The motorised flue damper has a chamfer on the male end for inserting into a flue piece and a lip seal on the female end to receive another section of flue Note The 150mm diameter motorised flue damper is for use with 80kW 120kW and 160kW Imax Xtra 2 boilers The 200mm ...

Page 3: ...the wiring to the flue damper PCB as follows 1 Thread the five wires though the cable grommet located on the Flue Damper Control box 2 Connect the Live wire to Pin 1 of the screw terminal of the flue damper PCB 3 Connect the Neutral wire to Pin 2 of the screw terminal of the flue damper PCB 4 Connect the Earth wire to the earthing point of the Flue Damper 5 Connect the Flue Damper Signal wire to P...

Page 4: ... connector I3_CN from Installation Connection I3 2 Connect the Live wire to Pin 3 of connector I3_CN 3 Connect the Neutral wire to Pin 2 of connector I3_CN 4 Connect the Earth wire to Pin 1 of connector I3_CN 5 Push connector I3_CN back into Installation Connection I3 6 Remove connector I12_CN_B from Installation Connection I12 7 Connect the Flue Damper Signal wire to Pin 1 of connector I12_CN_B 8...

Page 5: ...the wiring for the Flue Damper Turn on the power to the boiler and recommission the boiler to configure the connected motorised flue damper Power from main supply MUST be the same phase as the boiler supply Note If you are adding a Motorised Flue Damper to an Imax Xtra 2 that already has a Boiler Pump controlled directly from the boiler you must observe the following The On Off Controlled Boiler P...

Page 6: ...tion If you are installing an electrically operated flue damper onto a boiler that does not require boiler pump control then you can select No Boiler Pump This is done at the Boiler Pump page shown by selecting the No Boiler Pump option For either of the selections above you can now configure the Flue Damper This is done at the Cascade Flue with Electronic Damper Control page shown by selecting th...

Page 7: ...7 IMAX XTRA 2 Flue Damper Kit Instructions INSTRUCTIONS ...

Page 8: ...er an ISO 9001 registered quality management system FM 59915 At Ideal Heating we take our environmental impact seriously therefore when installing any Ideal Heating product please make sure to dispose of any previous appliance in an environmentally conscious manner Households can contact their local authority to find out how See https www gov uk managing your waste an overview for guidance on how ...