![background image](http://html1.mh-extra.com/html/ideal-heating/ecomod-ahp60-14-kw/ecomod-ahp60-14-kw_installation-and-servicing_3613961006.webp)
6 / 70
00U07352240-A_ EN
01-07-2022
7 / 70
1.2.2. Unpacking the appliance
Acceptance
With the carrier present, carefully check the general appearance of the packaging and the
appliances. Check that the outdoor appliance has not been placed in a horizontal position.
In the event of disagreement, write to the carrier within 48 hours mentioning all reserves and
send a copy of this letter to the After Sales Department.
Before unpacking the appliance, check that there are no refrigerant leaks using a suitable
detector. Check that there are no ignition sources near the unit.
Smoking is forbidden near to the unit.
1.2.3. Safety recommendations related to the presence of the R32 refrigerant
The handling and installation of this outdoor appliance must only be performed by personnel
that are duly trained, qualified and authorised to carry out these operations, according to the
laws, directives and standards applicable in each country.
The EN378:2016 standard defines the framework of requirements to be met to manage each
potential risk at each stage of the machine's life cycle. This standard was also used to design
this machine.
In the absence of local building codes or safety standards, the installation and maintenance of
the machine may follow the elements outlined in this standard; in particular, it is the responsibility
of the installer and personnel performing operations on this machine to perform a risk analysis
prior to any installation and work on the machine.
The elements indicated below are not exhaustive given the diversity of the possible
installations and interventions; they cannot be considered as an undertaking as to the
responsibility of Ideal heating. These elements cannot replace a risk analysis, which
remains the responsibility of the installer and the personnel working on the machines.
Designation
R32.
INDICATION OF DANGERS
Main dangers:
Asphyxia.
Specific dangers:
The rapidity of evaporation can cause burns.
EMERGENCY MEASURES
General information
Do not give anything to persons who have fainted.
Inhalation:
Take the person to fresh air.
Use oxygen or artificial respiration if required.
Do not administer adrenaline or similar substances.
Contact with the eyes:
Rinse thoroughly with water for at least 15 minutes and seek
medical attention.
Contact with the skin:
Rinse thoroughly with water for at least 15 minutes. Apply a sterile
gauze.
Remove contaminated clothing immediately.
FIRE PREVENTION MEASURES
Extinguishers:
Water spray, dry powder.
Specific dangers:
Rupture or explosion of the recipient.
Specific methods:
Cool down the recipients by spraying with water from a safe
position. If possible, stop the product from leaking. If possible, use
a water spray to hose down the smoke. Move the recipients well
clear of the fire zone if possible without taking risks.
MEASURES IN THE EVENT OF AN ACCIDENTAL LEAK
Individual precautions:
Use personal protection equipment.
Evacuate the personnel to safe areas.
Eliminate ignition sources.
Ensure there is adequate ventilation.
Environmental precautions:
Try to stop the leak.
Cleaning methods:
Ventilate the area.