12
Procombi Exclusive
-
Installation and Servicing
general
The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load of at least 10% of the
minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available. See
note regarding thermostatic radiator valves on page 9.
Note.
Systems incorporating zone valves which could completely cut off the flow through the system must also include a bypass.
3 sysTEM baLaNCINg
2 ...............CONTINUED
baLaNCINg
1.
Set the programmer to ON.
Close the manual or thermostatic valves on all radiators,
leaving the twin lockshield valves (on the radiators referred to
above) in the
OPEN position.
Turn up the room thermostat and adjust the lockshield valve
to give an uninterrupted flow through the radiator.
4 WaTER TREaTMENT
CENTRaL hEaTINg
The range of boilers have an ALUMINIUM
alloy heat
exchanger.
IMpORTaNT.
The application of any other treatment to this product
may render the guarantee of procombi Invalid.
procombi
recommend Water Treatment in accordance
with the Benchmark Guidance Notes on Water Treatment in
Central Heating Systems.
If water treatment is used
procombi
recommend only
the use of Scalemaster Gold 100,
FERNOx-MB-1, ADEY
MC1 SENTINEL-x100 or CALMAG CM100
inhibitors and
associated water treatment products, which must be used in
accordance with the manufacturers’ instructions.
Notes.
1.
It is most important that the correct concentration of the
water treatment products is maintained in accordance
with the manufacturers’ instructions.
2.
If the boiler is installed in an existing system any
unsuitable additives MUST be removed by thorough
cleansing. BS 7593:2006 details the steps necessary to
clean a domestic heating system.
3.
In hard water areas, treatment to prevent lime scale may
be necessary - however the use of artificially softened
water is NOT permitted.
4.
Under no circumstances should the boiler be fired
before the system has been thoroughly flushed.
DOMEsTIC hOT WaTER
In hard water areas where mains water can exceed 200ppm Total Hardness
(as defined by BS 7593:2006 Table 2) a scale reducing
device together with
Scalemaster in-line scale inhibitor
should be fitted into the boiler cold supply
within the requirements of the local water company. The use of artificially
softened water, however, is not permitted.
procombi
recommend the use of Fernox Quantomat, Sentinel Combiguard
and Calmag CalPhos I scale reducing devices, which must be used in
accordance with the manufacturers’ instructions.
These valves should now be left as set.
2.
Open all manual or thermostatic radiator valves and
adjust the lockshield valves on the remaining radiators, to
give around 20
o
C temperature drop at each radiator.
3.
Adjust the room thermostat and programmer to
NORMAL settings.
DOMEsTIC hOT WaTER
1.
The domestic hot water service must be in accordance with
BS 5546 and BS 6700.
2.
Refer to Table 1 for minimum and maximum working
pressures. In areas of low mains water pressures the
domestic hot water regulator may be removed from the
DHW flow turbine cartridge. Refer to Frame 61. The boiler
will require the flow rate to be set to obtain a temperature
rise of 35
o
C at the tap furthest from the boiler.
3.
The boilers are suitable for connection to most types of
washing machine and dishwasher appliances.
4.
When connecting to suitable showers, ensure that:
a.
The cold inlet to the boiler is fitted with an approved
anti-vacuum or syphon non-return valve.
b.
Hot and cold water supplies to the shower are of equal
pressure.
5. hard Water areas -
Where the water hardness exceeds
200mg/litre (200ppm), it is recommended that a proprietary
scale reducing device is fitted into the boiler cold supply
within the requirements of the local water company.
IMpORTaNT
Provision MUST be made to accomodate the expansion of DHW
contained within the appliance. If the DHW inlet contains a back
flow prevention device or non-return valve, e.g. a water meter,
then a mini expansion vessel should be fitted between the device
and the boiler in the cold inlet pipe.
Cold water, rising main and pipework on exposed areas need to
be suitably lagged to prevent freezing.
Note.
DHW Expansion Vessel Kit availabe from Procombi.
For further information contact:
Fernox Cookson Electronics
Forsyth Road, Sheerwater, Woking, Surrey GU21 5RZ
+44 (0) 8706 015000
Sentinel Performance Solutions
The Heath Business & Technical Park, Runcorn, Cheshire WA7 4Qx
Tel: 0800 389 4670
Scalemaster Water Treatment Products
Emerald Way, Stone, Staffordshire ST15 0SR
Tel: +44 (0) 1785 811636
Calmag Ltd.
Unit 3-6, Crown Works, Bradford Road,
Sandbeds, Keighley, West Yorkshire BD20 5LN
Tel: +44 (0) 1535 210320
Adey Professional Heating Solutions
Gloucester Road, Cheltenham GL51 8NR
Tel: +44 (0) 1242 546700