13
Mexico Super RS440 - RS470 -
Installation & Servicing
INSTALLATION
9
BOILER CASING REMOVAL
Mex 1947
Side view of boiler
sections showing the
baffle arrangements
RS 470
RS 440
RS 450 & RS 460
1.
Remove the flue cleanout cover.
2.
Ensure that the baffles are fully inserted in the flueways.
10 CHECKING THE FLUEWAY BAFFLES
MEX 1941
5
2
1
Control
panel
Grille
Assy.
To install the boiler the casing MUST be removed.
1.
Undo the 2 screws and lift off the lower front
panel.
2.
Remove 2 screws and lift off the grille assembly.
3.
Disconnect the in-line connector on the PCB
lead.
4.
Remove the Burner On neon cable from the
back of the control panel.
5.
Remove the 2 screws securing the control panel
and disengage the panel by lowering and
pulling it forward.
6.
Remove the 2 screws securing the top panel to
the side.
7.
Draw the top panel forward and lift it off the
boiler.
8.
Remove the 2 screws securing the LH side
panel to the flue collector and baseplate.
9.
Pull the panel forward, lifting it clear of the
locating peg and remove.
10.
Repeat steps 8 and 9 to remove the RH panel.
11.
The boiler is held to the packaging base by 4 x
M6 hex head screws. Remove the front screws,
slacken the rear screws and remove the boiler
from the packaging base.
MEX 218
0
7
8
6
11
8
MEX 1930
Baffles
Cleanout cover
INST
ALLA
TION
200941-1.p65
3/3/2004, 10:25 AM
13