Harrier GTS, Viceroy GTS, Viscount GTS - 

User's

1

BOILER CONTROLS

2

CONTROL OF WATER TEMPERATURE

The water temperature is controlled by the boiler thermostat (item 3A).  The temperature range of the thermostat is 30 - 90

o

C for

ON/OFF operation.  For boilers fitted with high/low burners, a 2nd stage thermostat controls the burner changeover from high to
low fire at a recommended setting 5

o

C lower than the maximum flow temperature setting.

Note.

The setting numbers 3-9 are approximately scaled to represent 30-90

o

C.

To Light the Boiler  

(Refer to Frame 1)

1.

CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
IS OFF.

2.

Set the boiler on/off switch (1) to OFF.

3.

Set the boiler flow temperature control (3A) to maximum (1st
stage control if high/low burner fitted).

4.

Switch on the electricity supply to the boiler and check that all
external controls, e.g. programmer, room thermostat etc., are
on.

5.

Set the boiler on/off switch (1) to ON.

The boiler will commence the ignition sequence, supplying
heat to the system when required.

Note.

 

 If the burner does not ignite refer to the burner

instructions.

6.

Set the boiler flow temperature control (3A) to the desired
setting.  If a high/low burner is fitted, set the 2nd stage
temperature control (3B) to a setting 5

o

C lower.

Settings below 4 (approx. 40

o

C) are not recommended, in

order to avoid the risk of combustion products condensing
on the walls of the boiler.

7. Burner

Refer to the instructions supplied with the burner for specific
control features.

7

6

2

1

3A

3B

4

5

har9096

1.

Boiler ON/OFF switch.

Position      .....ON Position     .....OFF

2.

TEST STB:

When held in the pressed (momentary use) position it
tests the safety thermostat.

Note. 

If two stage burner control fitted operation will

continue on 1st stage after 2nd stage cut-off.

3.

Boiler Thermostats:

Adjustment range 30-90

o

C

For ON/OFF burners use 1st stage thermostat only.

For two stage burners set 2nd stage 5

o

C below 1st

stage setting.

4.

Boiler Thermometer

5.

Location for Flue Gas Thermometer (Optional)

6.

Timed Circuit Breaker:

10A with delayed action and manual reset.

7.

Safety Thermostat:

Set at 110

o

C.  Manual reset.

Summary of Contents for Harrier GTS

Page 1: ... on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers Harrier GTS Viceroy GTS Viscount GTS All Models 300014486 001 A ...

Page 2: ...ppliance In cases of repeated or continuous shutdown a recognised installer CORGI registered for gas fired boilers should be called to investigate and rectify the condition causing this and carry out an operational test after each intervention on the device Only the manufacturer s original parts should be used for replacement Minimum Clearances Harrier GTS Clearances of 1000mm 40 at the rear 200mm...

Page 3: ...nce the ignition sequence supplying heat to the system when required Note If the burner does not ignite refer to the burner instructions 6 Set the boiler flow temperature control 3A to the desired setting If a high low burner is fitted set the 2nd stage temperature control 3B to a setting 5o C lower Settings below 4 approx 40o C are not recommended in order to avoid the risk of combustion products...

Page 4: ...eating is detected by the overheat thermostat connected to the boiler control module If the boiler has overheated allow it to cool then press the safety thermostat reset button under the screw top cap 7 and the burner will relight If the fault recurs turn off the boiler and consult a recognised installer CORGI registered for gas fired boilers Escape of Gas Should a gas leak or fault be suspected c...

Reviews: