2
Harrier GTE -
User's
Harrier GTE
(Gas and Fuel Oil)
PI No.
49AQ950
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded
in your Log Book. You can check your installer by calling CORGI direct on 0156 372 300.
INTRODUCTION
The
Harrier GTE
is a floor-standing boiler featuring full
sequence automatic gas or fuel oil burner.
SAFETY
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
FOR GAS FIRED BOILERS
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed and maintained by a CORGI registered
installer, in accordance with the above regulations.
The appliance should be serviced at least once a year by a
CORGI registered installer.
Electricity Supply
The appliance must be earthed.
Supply 230 V - 50 Hz.
The appliance is intended to be connected to the supply via a
double-pole switch, having a 3mm contact separation in both
poles, serving only the boiler and system controls. Alternatively,
a 3-pin UNSWITCHED socket may be used.
The burner and circulating pumps may be 1ph or 3ph.
Important Notes
•
Do not store objects around or on the boiler, and keep
access clear at all times.
•
Do not obstruct ventilation ducts, grilles or openings in the
boiler room or the passage of combustion and ventilation air
to the boiler.
•
Do not turn off the boiler if it is to be left unattended in frosty
weather.
•
If it is known or suspected that a fault exists on the boiler
then it MUST NOT BE USED until the fault has been
corrected by a recognised installer (CORGI registered for
gas-fired boilers).
•
Flammable materials must not be placed in close proximity
to the appliance. Materials giving off flammable vapours
must not be stored in the same room as the appliance.
In cases of repeated or continuous shutdown, a recognised
installer (CORGI registered for gas-fired boilers) should be
called to investigate and rectify the condition causing this and
carry out an operational test after each intervention on the
device. Only the manufacturer's original parts should be used for
replacement.
Minimum Clearances
Clearances of
1000mm (40")
at the rear, 200mm (8") plus
burner projection on burner hinge side or
500mm (20")
whichever is the greater on one side and
100mm (4")
on the
other side and
1500mm (60")
at the front of the boiler casing
must be allowed for servicing.
To Light the Boiler
(Refer to Frame 1)
1.
CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
IS OFF.
2.
Set the boiler on/off switch (1) to OFF.
3.
Set the boiler flow temperature control (3A) to maximum (1st
stage control if high/low burner fitted).
4.
Switch on the electricity supply to the boiler and check that all
external controls, e.g. programmer, room thermostat etc., are
on.
If a Deluxe control panel is fitted set the Burner and Pump
switch (2) to Winter, the Auto/Manual/Test switch (5) to Auto or
Manual and the Stage switch (6) to 2.
.
5.
Set the boiler on/off switch (1) to ON.
The boiler will commence the ignition sequence, supplying
heat to the system when required.
Note.
If the burner does not ignite refer to the burner
instructions.
6.
Set the boiler flow temperature control (3A) to the desired
setting. If a high/low burner is fitted, set the 2nd stage
temperature control (3B) to a setting 5ºC lower.
Settings below 4 (approx. 40ºC) are not recommended, in
order to avoid the risk of combustion products condensing
on the walls of the boiler.
If a Deluxe control panel is fitted set the Burner and Pump
Summer/Winter switch (2) and Stage switch (6) to the
desired setting.
7. Burner
Refer to the instructions supplied with the burner for specific
control features.
Destination Countries:
GB, IE