background image

3

SAFETY PRECAUTIONS

READ SAFETY PRECAUTIONS BEFORE INSTALLATION:

Incorrect installation due to ignoring instructions can cause serious damage or injury.

The seriousness of potential damage or injuries is classified as either a 

WARNING

 or 

CAUTION

.

 WARNING

•  DO NOT

 modify the length of the power supply cord or use an extension cord to power the unit.

•  DO NOT

 share the electrical outlet with other appliances. Improper or insufficient power supply

  can cause fire or electrical shock.
•  When connecting refrigerant piping,

 DO NOT

 let substances or gases other than the specified

  refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
  and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.

•  DO NOT

 allow children to play with the air conditioner. Children must be supervised around the

  unit at all times.
•  Installation must be performed by a certified service technician. Defective installation can cause 
  water leakage, electrical shock, or fire.
•  Installation must be performed according to the installation instructions. Improper installation can
  cause water leakage, electrical shock, or fire. (In North America, installation must be performed in 
  accordance with the requirement of NEC and CEC by authorized personnel only.)
•  Contact an authorized service technician for repair or maintenance of this unit.
•  Only use the included accessories, parts, and specified parts for installation. Using non-standard parts 
  can cause water leakage, electrical shock, fire, and can cause the unit to fail.
•  Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot
  support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious 
  injury and damage.
•  For all electrical work, follow all local and national wiring standards, regulations, and the Installation 
  Manual. You must use an independent circuit and single outlet to supply power. 

DO NOT

 connect other 

  appliances to the same outlet. Insufficient electrical capacity or defects in electrical work can cause 
  electrical shock or fire.
•  For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to
  prevent external forces from damaging the terminal. Improper electrical connections can overheat and 
  cause fire, and may also cause shock.
•  All wiring must be properly arranged to ensure that the control board cover can close properly. If the 
  control board cover is not closed properly, it can lead to corrosion and cause the connection points on 
  the terminal to heat up, catch fire, or cause electrical shock.
•  In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed
  air-conditioning units is highly recommended.
•  If the supply cord is damaged, it must be replaced by a certified service technician or similarly
  qualified persons in order to avoid a hazard.

This symbol indicates that 

ignoring instructions may cause 

damage to your unit, or other 

property, serious injury or death.

This symbol indicates that ignoring 

instructions may cause moderate 

injury to you, or damage to your 

unit or other property.

WARNING

CAUTION

Summary of Contents for PRO

Page 1: ...NER INSTALLATION MANUAL This manual only describes the installation of the indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit 700807 700808 PRO MINI SPLIT I...

Page 2: ...ur purchase of Ideal Air s Pro Mini Split indoor wall mount unit We re proud to offer this product and believe it s the very best in its class 2 SAFETY PRECAUTIONS 3 ACCESSORIES 5 INSTALLATION SUMMARY...

Page 3: ...n cause water leakage electrical shock fire and can cause the unit to fail Install the unit in a firm location that can support the unit s weight If the chosen location cannot support the unit s weigh...

Page 4: ...UTION NOTE ABOUT FLUORINATED GASES This air conditioning unit contains fluorinated gases For specific information on the type of gas and the amount please refer to the relevant label on the unit itsel...

Page 5: ...nd fire or equipment failure Name Shape Quantity 1 1 1 Clip anchor Mounting plate fixing screw ST3 9 X 25 Remote control Fixing screw for remote control holder ST2 9 x 10 Remote control holder Dry bat...

Page 6: ...tion Page 9 And Drill Wall Hole Page 10 1 Attach Mounting Plate Page 10 2 Prepare Refrigerant Piping Page 12 4 3b 12cm 4 75 2 3m 90 55 12cm 4 75 15cm 5 9 Determine Wall Hole Position Page 10 3a INSTAL...

Page 7: ...7 Mount Indoor Unit Page 16 STEP 8 Wrap Piping and Cable Page 15 1 2 3 Connect Drain Hose Page 13 Connect Signal Cable Page 14 5 6 7 8...

Page 8: ...nt Panel Outdoor Unit Power Cable Some Units Remote Holder Remote Control Some Units UNIT PARTS NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your...

Page 9: ...t the weight of the unit A location at least 1m 40 from all other electrical devices e g TV radio computer DO NOT INSTALL UNIT IN THE FOLLOWING LOCATIONS Near any source of heat steam or combustible g...

Page 10: ...2 5 core drill drill a hole in the wall Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 5mm 7mm 0 2 0 275 This...

Page 11: ...m 1 55 Right rear wall hole 65mm 2 5 Model C 965mm 38 138mm 5 45 34mm 1 35 517 4mm 20 37 Indoor unit outline Left rear wall hole 65mm 2 5 219mm 8 6 553mm 21 77 300mm 11 8in 335mm 13 2 Right rear wall...

Page 12: ...ILL AFFECT THE UNIT S PERFORMANCE Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6 of the refrigerant piping This serves two purposes a To facilitate the Refrigerant...

Page 13: ...a small amount of water into the drain pan to make sure that water flows from the unit smoothly PLUG THE UNUSED DRAIN HOLE To prevent unwanted leaks you must plug the unused drain hole with the rubber...

Page 14: ...it to an individual branch circuit outlet DO NOT connect another appliance to that outlet Make sure to properly ground the air conditioner Every wire must be firmly connected Loose wiring can cause th...

Page 15: ...he wire cover on the front of the unit and the plastic panel on the back STEP 7 WRAP PIPING AND CABLES Before passing the piping drain hose and the signal cable through the wall hole you must bundle t...

Page 16: ...dded in the wall do the following Hook the top of the indoor unit on the upper hook of the mounting plate Use a bracket or wedge to prop up the unit giving you enough room to connect the refrigerant p...

Page 17: ...e to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See FIG 4 2 and FIG 4 3 above INSTALLATION INSTRUCTIONS OUTDOOR UNIT IF THE UNIT...

Page 18: ...etween their mounting feet Prepare the installation base of the unit according to the dimensions below FIG 4 4 WARNING W A B D Air inlet Air outlet Air inlet Outdoor Unit Dimensions mm in W x H x D Mo...

Page 19: ...1 5 times the maximum current of the unit If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 3mm 125 must be incorpora...

Page 20: ...and place it to the side Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal After checking to make sure every conn...

Page 21: ...of 5m 16 5 Refer to the table below for specifications on the maximum length and drop height of piping MAXIMUM LENGTH AND DROP HEIGHT OF REFRIGERANT PIPING PER UNIT MODEL DO NOT DEFORM PIPE WHILE CUTT...

Page 22: ...or cracks and even flaring STEP 4 CONNECT PIPES When connecting refrigerant pipes be careful not to use excessive torque or to deform the piping in any way You should first connect the low pressure pi...

Page 23: ...quirements shown in the table above WARNING TORQUE REQUIREMENTS Outer Diameter of Pipe mm Tightening Torque N cm Add Tightening Torque N m 6 35 0 25 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4...

Page 24: ...Using hexagonal wrench fully open both the high pressure and low pressure valves Tighten valve caps on all three valves service port high pressure low pressure by hand You may tighten it further usin...

Page 25: ...CODES AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN GAS LEAK CHECKS There are two different methods to check for gas leaks SOAP AND WATER METHOD Using a soft brush apply soapy water or liquid deter...

Page 26: ...ent temperature is below 17 C In this instance you can use the MANUAL CONTROL button to test the COOL function Lift the front panel of the indoor unit and raise it until it clicks in place The MANUAL...

Page 27: ...greater the number rating the more efficient the heating A 10 HSPF for example is a very good rating Humidifier Humidifiers use water to put humidity in the growing space Many plants we grow indoors a...

Page 28: ...answers to most common questions and a complete technical support library please visit www ideal air com All design and specifications herein are subject to change without notice for product improveme...

Reviews: