background image

IF YOU WILL INSTALL THE UNIT ON THE 

GROUND OR ON A CONCRETE MOUNTING 

PLATFORM, DO THE FOLLOWING:

•  Mark the positions for four expansion bolts based 
  on dimensions in the Unit Mounting Dimensions chart.
•  Pre-drill holes for expansion bolts.
•  Clean concrete dust away from holes.
•  Place a nut on the end of each expansion bolt.
•  Hammer expansion bolts into the pre-drilled holes.
•  Remove the nuts from expansion bolts, and place 
  outdoor unit on bolts.
•  Put washer on each expansion bolt, then replace
  the nuts.
•  Using a wrench, tighten each nut until snug.
•  Ensure the unit is level.

STEP 4: CONNECT SIGNAL AND POWER 

CABLES

The outside unit’s terminal block is protected by

an electrical wiring cover on the side of the unit.

A comprehensive wiring diagram is printed on

the inside of the wiring cover.

BEFORE PERFORMING ELECTRICAL 

WORK, READ THESE REGULATIONS

•  All wiring must comply with local and national 
  electrical codes, and must be installed by a licensed 
 electrician.
•  All electrical connections must be made according 
  to the Electrical Connection Diagram located on the 
  side panels of the indoor and outdoor units.
•  If there is a serious safety issue with the power 
  supply, stop work immediately. Explain your reasoning 
  to the client, and refuse to install the unit until the 
  safety issue is properly resolved.
•  Power voltage should be within 90-100% of rated 
  voltage. Insufficient power supply can cause 
  electrical shock or fire.
•  If connecting power to fixed wiring, install a surge 
  protector (Ideal-Air

TM

 700522) and main power 

  switch with a capacity of 1.5 times the maximum 
  current of the unit.
•  If connecting power to fixed wiring, a switch or 
  circuit breaker that disconnects all poles and has a 
  contact separation of at least 3mm/.125" must be 
  incorporated in the fixed wiring. The qualified technician 
  must use an approved circuit breaker or switch.
•  Only connect the unit to an individual branch 
  circuit outlet. 

DO NOT

 connect another appliance 

  to that outlet.
•  Make sure to properly ground the air conditioner.
•  Every wire must be firmly connected. Loose wiring 
  can cause the terminal to overheat, resulting in 
  product malfunction and possible fire.
• 

DO NOT

 let wires touch or rest against refrigerant 

  tubing, the compressor, or any moving parts within 
  the unit.

Before installing a wall-mounted unit, make sure that 
the wall is made of solid brick, concrete, or of similarly 
strong material. 

The wall must be able to support 

at least four times the weight of the unit.

•  Mark the position of bracket holes based on
  dimensions in the Unit Mounting Dimensions chart.
•  Pre-drill the holes for the expansion bolts.
•  Clean dust and debris away from holes.
•  Place a washer and nut on the end of each
  expansion bolt.
•  Thread expansion bolts through holes in mounting 
  brackets, put mounting brackets in position, and 
  hammer expansion bolts into the wall.
•  Check that the mounting brackets are level.
•  Carefully lift unit and place its mounting feet
  on brackets.
•  Bolt the unit firmly to the brackets.

TO REDUCE VIBRATIONS OF 

WALL MOUNTED UNIT

If allowed, you can install the wall-mounted unit with 
rubber gaskets to reduce vibrations and noise.

WHEN DRILLING INTO CONCRETE, EYE

PROTECTION IS RECOMMENDED AT ALL

TIMES.

IF YOU WILL INSTALL THE UNIT ON A 

WALL-MOUNTED BRACKET, DO THE  

FOLLOWING:

 WARNING

 WARNING

CAUTION

bt

Summary of Contents for PRO

Page 1: ...NER INSTALLATION MANUAL This manual only describes the installation of the indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit 700807 700808 PRO MINI SPLIT I...

Page 2: ...ur purchase of Ideal Air s Pro Mini Split indoor wall mount unit We re proud to offer this product and believe it s the very best in its class 2 SAFETY PRECAUTIONS 3 ACCESSORIES 5 INSTALLATION SUMMARY...

Page 3: ...n cause water leakage electrical shock fire and can cause the unit to fail Install the unit in a firm location that can support the unit s weight If the chosen location cannot support the unit s weigh...

Page 4: ...UTION NOTE ABOUT FLUORINATED GASES This air conditioning unit contains fluorinated gases For specific information on the type of gas and the amount please refer to the relevant label on the unit itsel...

Page 5: ...nd fire or equipment failure Name Shape Quantity 1 1 1 Clip anchor Mounting plate fixing screw ST3 9 X 25 Remote control Fixing screw for remote control holder ST2 9 x 10 Remote control holder Dry bat...

Page 6: ...tion Page 9 And Drill Wall Hole Page 10 1 Attach Mounting Plate Page 10 2 Prepare Refrigerant Piping Page 12 4 3b 12cm 4 75 2 3m 90 55 12cm 4 75 15cm 5 9 Determine Wall Hole Position Page 10 3a INSTAL...

Page 7: ...7 Mount Indoor Unit Page 16 STEP 8 Wrap Piping and Cable Page 15 1 2 3 Connect Drain Hose Page 13 Connect Signal Cable Page 14 5 6 7 8...

Page 8: ...nt Panel Outdoor Unit Power Cable Some Units Remote Holder Remote Control Some Units UNIT PARTS NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your...

Page 9: ...t the weight of the unit A location at least 1m 40 from all other electrical devices e g TV radio computer DO NOT INSTALL UNIT IN THE FOLLOWING LOCATIONS Near any source of heat steam or combustible g...

Page 10: ...2 5 core drill drill a hole in the wall Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 5mm 7mm 0 2 0 275 This...

Page 11: ...m 1 55 Right rear wall hole 65mm 2 5 Model C 965mm 38 138mm 5 45 34mm 1 35 517 4mm 20 37 Indoor unit outline Left rear wall hole 65mm 2 5 219mm 8 6 553mm 21 77 300mm 11 8in 335mm 13 2 Right rear wall...

Page 12: ...ILL AFFECT THE UNIT S PERFORMANCE Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6 of the refrigerant piping This serves two purposes a To facilitate the Refrigerant...

Page 13: ...a small amount of water into the drain pan to make sure that water flows from the unit smoothly PLUG THE UNUSED DRAIN HOLE To prevent unwanted leaks you must plug the unused drain hole with the rubber...

Page 14: ...it to an individual branch circuit outlet DO NOT connect another appliance to that outlet Make sure to properly ground the air conditioner Every wire must be firmly connected Loose wiring can cause th...

Page 15: ...he wire cover on the front of the unit and the plastic panel on the back STEP 7 WRAP PIPING AND CABLES Before passing the piping drain hose and the signal cable through the wall hole you must bundle t...

Page 16: ...dded in the wall do the following Hook the top of the indoor unit on the upper hook of the mounting plate Use a bracket or wedge to prop up the unit giving you enough room to connect the refrigerant p...

Page 17: ...e to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See FIG 4 2 and FIG 4 3 above INSTALLATION INSTRUCTIONS OUTDOOR UNIT IF THE UNIT...

Page 18: ...etween their mounting feet Prepare the installation base of the unit according to the dimensions below FIG 4 4 WARNING W A B D Air inlet Air outlet Air inlet Outdoor Unit Dimensions mm in W x H x D Mo...

Page 19: ...1 5 times the maximum current of the unit If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 3mm 125 must be incorpora...

Page 20: ...and place it to the side Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal After checking to make sure every conn...

Page 21: ...of 5m 16 5 Refer to the table below for specifications on the maximum length and drop height of piping MAXIMUM LENGTH AND DROP HEIGHT OF REFRIGERANT PIPING PER UNIT MODEL DO NOT DEFORM PIPE WHILE CUTT...

Page 22: ...or cracks and even flaring STEP 4 CONNECT PIPES When connecting refrigerant pipes be careful not to use excessive torque or to deform the piping in any way You should first connect the low pressure pi...

Page 23: ...quirements shown in the table above WARNING TORQUE REQUIREMENTS Outer Diameter of Pipe mm Tightening Torque N cm Add Tightening Torque N m 6 35 0 25 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4...

Page 24: ...Using hexagonal wrench fully open both the high pressure and low pressure valves Tighten valve caps on all three valves service port high pressure low pressure by hand You may tighten it further usin...

Page 25: ...CODES AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN GAS LEAK CHECKS There are two different methods to check for gas leaks SOAP AND WATER METHOD Using a soft brush apply soapy water or liquid deter...

Page 26: ...ent temperature is below 17 C In this instance you can use the MANUAL CONTROL button to test the COOL function Lift the front panel of the indoor unit and raise it until it clicks in place The MANUAL...

Page 27: ...greater the number rating the more efficient the heating A 10 HSPF for example is a very good rating Humidifier Humidifiers use water to put humidity in the growing space Many plants we grow indoors a...

Page 28: ...answers to most common questions and a complete technical support library please visit www ideal air com All design and specifications herein are subject to change without notice for product improveme...

Reviews: