background image

Sensor Interface

The analog expander allows the control of four separate analog input channels which can be used interface with
any industrial automation sensor that provides a 4-20mA or 0-10V output. The results from the sensor can be
used to control any number of programmable functions in the Protege system.

There are common requirements when wiring sensor inputs that must be observed to ensure the highest
possible performance is achieved.

All cables should be high quality overall screened instrumentation rated cable with the screen earthed at

one

end only.

Signal cables should be laid a minimum distance of 300mm from any source of interference including power
cables, high current conductors, switchgear, or any forms of electrical noise.

For two-wire sensor loops we recommend Austral standard cable B5102ES. For three-wire loops we
recommend Austral standard cable B5103ES.

It is recommended that you do not ground any current loop output, and use of a power supply that does not
require a ground connection is recommended.

If possible, signal-carrying cable that is exposed to harsh environments should include extra precaution
against lightning strikes.

We recommend operating the module and associated sensors using a non-grounded power supply unit. Before
removing ground connections for power supplies ensure that local regulations for the region allow this
connection.

Sensor Input 0-10V Interface

The analog expander allows the connection of voltage output sensors.

The acceptable signal range is from 0-10V. This is translated by the analog expander into a digital value which
can be used in the programmable functions and variable display in the Protege software. It is also possible to
connect any device which outputs a voltage between these values (e.g. 0-5V) and utilize the scaling functions
within the Protege system.

The following example shows the connection of a 0-10V output daylight sensor. This device has a single 0-10V
output that represents the current brightness of daylight in lux detected by the sensor device. In this example
the sensor has been connected to Input 1 on the analog expander. The wiring is equivalent for all available
analog inputs.

V-

V+

OV

V+ = +24VDC

V- = 24VDC GROUND

0V = OUTPUT VOLTAGE

0-10V OUTPUT DAYLIGHT SENSOR

0-5K / 0-50K LUX DEVICE

V-

1i

24V+

2i

3i

V-

4i

V-

ANALOG EXPANDER

PRT-ADC4-DIN | Protege DIN Rail 4 Channel Analog Input Expander | Installation Manual

10

Summary of Contents for PRT-ADC4-DIN

Page 1: ...PRT ADC4 DIN Protege DIN Rail 4 Channel Analog Input Expander Installation Manual...

Page 2: ...ical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo are...

Page 3: ...Inputs 12 Address Configuration 13 LED Indicators 14 Status Indicator 14 Fault Indicator 14 Power Indicator 14 Analog Input Status Indicators 14 Error Code Indication 15 Error Code Display 15 Mechanic...

Page 4: ...combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module The current features of the analog expander include 4 independen...

Page 5: ...is to be installed in accordance with The product installation instructions AS NZS 2201 1 Intruder Alarm Systems The Local Authority Having Jurisdiction AHJ PRT ADC4 DIN Protege DIN Rail 4 Channel Ana...

Page 6: ...wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installation A...

Page 7: ...k Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note tha...

Page 8: ...lled in an electrical room communication equipment room secure cabinet or in an accessible area of the ceiling 1 Position the DIN rail module with the labeling in the correct orientation 2 Hook the mo...

Page 9: ...e to all devices on the RS 485 network Warning The 12V N and N communication input must be supplied from only one point Connections from more than one 12V supply may cause failure or damage to the uni...

Page 10: ...ents should include extra precaution against lightning strikes We recommend operating the module and associated sensors using a non grounded power supply unit Before removing ground connections for po...

Page 11: ...utilize the scaling functions within the Protege system The following example shows the connection of a 4 20mA output daylight sensor This device has a current loop 4 20mA output that represents the c...

Page 12: ...nputs Trouble inputs are used to monitor the module status and in most cases are not physically connected to an external input The following table details the trouble inputs that are configured in the...

Page 13: ...oduct Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When adding an...

Page 14: ...mware update or is in firmware update mode When the fault indicator is on the status indicator will flash an error code State Description Continuous slow flash red Module is in boot mode awaiting firm...

Page 15: ...ature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the ra...

Page 16: ...3 4 1 N N NA NB 24V V 5i 12VDC IN RS485 NETWORK 24VDC OUT ANALOG INPUT 5 8 24V 24VDC OUT 5 6 7 8 2 3 4 1 5 6 7 8 ANALOG IN ANALOG OUT V 6i 7i V 8i V 1i V 2i 3i V 4i ANALOG INPUT 1 4 Status Indicators...

Page 17: ...ils needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 156 80 44 68 Front 139 18 72 00 2x 4 67 Screw Hole 17 03 42 40 42 40 156 80 35 40 Back PRT A...

Page 18: ...esolution Trouble Inputs 8 Dimensions Dimensions L x W x H 156 8 x 90 x 60mm 6 17 x 3 54 x 2 36 Weight 270g 9 52oz Operating Conditions Operating Temperature 5 55 Celsius 41 131 Fahrenheit Storage Tem...

Page 19: ...eral Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT ADC4 DIN Protege DIN Rail 4 Channel Analog Input Ex...

Page 20: ...andling Please contact your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your nat...

Page 21: ...r per input Do not mix unpowered detectors and non latching powered detectors on an input To comply with EN 50131 1 the Entry Timer should not be programmed to more than 45 seconds To comply with EN 5...

Page 22: ...vice may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES...

Page 23: ...003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT ADC4 DIN Protege DIN Rail 4 Channel Analog Input E...

Page 24: ...liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and...

Page 25: ...aimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circumstances to...

Reviews: