Protege DIN Rail 8 PGM Output Expander
| Installation Manual
29
ArmorIP detects the reception of any invalid packet on the programmed port as a potential system
compromise attempt. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
Account Code as defined in the Serial Receiver settings
Event Code 0x163
Group Code as defined in the Serial Receiver settings
Point Code as defined in the Serial Receiver settings
Refer to the section
Global Settings | Serial Receiver
in the ArmorIP Internet Monitoring Application User's
Manual (227-5500-000).
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the Compromise Attempt event.
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
UL294
The Models PRT-CTRL-DIN and PRT-RDM2-DIN are intended to be mounted within the enclosure (refer to
UL/ULC Installation Cabinet Options (see page 23)), installed inside the protected premise, and are UL 294
Listed for Attack Class I applications only
Exit devices and wiring must be installed within the protected area.
For the Models PRT-CTRL-DIN and PRT-RDM2-DIN, all RS485 and reader terminal connections must be
made using shielded grounded cable.
All readers must be connected with shielded, grounded cable.
A bell or visual indicator used as an arming acknowledgement signal must be listed to a UL security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to UL10B or
UL10C.
AC power on shall be indicated by an external panel mount LED (Lumex SSI-LXH312GD-150) and fitted into
a dedicated 4mm hole in the cabinet to provide external visibility. This shall be wired between 12V and a
PGM output that is programmed to follow the AC trouble input as shown below:
BZ
L1
D1
DO
LED
V+
V-
Z4
V-
Z3
Z2
V-
Z1
1K5 OHM
READER 1
ZONE INPUT 1-4
12VDC OUT
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.