7 Diagnostics and servicing
WIKA Operating Instructions - Process pressure transmitter CPT-2x
Code
Text message
Cause
Rectification
F264
Installation/Setup error
Inconsistent settings (e.g.: distance, ad-
justment units with application process
pressure) for selected application
Invalid sensor configuration (e.g.: ap
-
plication electronic differential pressure
with connected differential pressure
measuring cell)
Modify settings
Modify connected sensor configuration
or application
F265
Measurement function dis-
turbed
Sensor no longer carries out a meas-
urement
Carry out a reset
Disconnect operating voltage briefly
Tab. 5: Error codes and text messages, information on causes as well as corrective measures
Code
Text message
Cause
Rectification
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after
60 mins.
Code
Text message
Cause
Rectification
S600
Impermissible electronics
temperature
Temperature of the electronics in the
non-specified range
Check ambient temperature
Insulate electronics
Use instrument with higher tempera-
ture range
S603
Impermissible operating volt-
age
Operating voltage below specified
range
Check electrical connection
If necessary, increase operating voltage
S605
Impermissible pressure value
Measured process pressure below or
above the adjustment range
Check nominal measuring range of the
instrument
If necessary, use an instrument with a
higher measuring range
Tab. 7: Error codes and text messages, information on causes as well as corrective measures
Code
Text message
Cause
Rectification
M500
Error in the delivery status
The data could not be restored during
the reset to delivery status
Repeat reset
Load XML file with sensor data into the
sensor
M501
Error in the non-active lineari-
sation table
Index markers are not continuously ris-
ing, for example illogical value pairs
Check linearisation table
Delete table/Create new
Function check
Out of specification
Maintenance