![ICPDAS DL-100-E User Manual Download Page 67](http://html1.mh-extra.com/html/icpdas/dl-100-e/dl-100-e_user-manual_3510612067.webp)
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020
- 67 -
Address Description
Attribute
40873
The starting record to read log data, low word
R/W
40874
The starting record to read log data, high word
R/W
40875
The status of the data logging, 0: stopped, 1:
running
R
40876
The data logger command, 0: stop, 1: run, 2: run
in period mode
R/W
40877
Continue writing when data logger is full, 0: no, 1:
yes
R/W
40878
Hour of the data logger sampling period, 0 ~ 24 R/W
40879
Minute of the data logger sampling period, 0 ~ 59 R/W
40880
Second of the data logger sampling period, 0 ~
59
R/W
40881
Starting year when logging in period mode, 2000
~ 2159
R/W
40882
Starting month when logging in period mode, 1 ~
12
R/W
40883
Starting date when logging in period mode, 1 ~ 31 R/W
40884
Starting hour when logging in period mode, 0 ~ 23 R/W
40885
Starting minute when logging in period mode, 0 ~
59
R/W
40886
Starting second when logging in period mode, 0 ~
59
R/W
40887
Ending year when logging in period mode, 2000 ~
2159
R/W
40888
Ending month when logging in period mode, 1 ~
12
R/W
40889
Ending date when logging in period mode, 1 ~ 31 R/W
40890
Ending hour when logging in period mode, 0 ~ 23 R/W
40891
Ending minute when logging in period mode, 0 ~
59
R/W
40892
Ending second when logging in period mode, 0 ~
59
R/W