background image

 

 

Outdoor combustion air kit – chimney venting 

 

The following kit has been certified for use on this 
appliance. The kit contains an important safety feature, 
namely a vacuum relief valve, or VRV. During normal 
operation the burner aspirates outdoor air. If the intake 
terminal ever becomes partially blocked or fully blocked 
from ice or snow etc., the VRV will open to allow a 
proportion of air from the dwelling to enter the burner thus 
maintaining proper combustion. Once the blockage is 
removed, the VRV will close and the burner will draw all 
air from the outdoors again. 

 

CAS-2B

 Components (except air duct) for the Beckett 

AFG burner: The kit includes the intake terminal, vacuum 
relief valve (VRV) and special air boot connection with 
integral air adjustment means for the AFG burner. The 
CAS-2B can be used with a 0.10 m (4") galvanized steel 
air duct or with a 0.10 m (4") flexible aluminium air duct. It 
is recommended that the metallic air ducting material be 
insulated from the air intake up to 1.5 m (5') from the 
burner, to avoid condensation on the outside of the intake 
pipe.  

 

CAD-1

  This air duct kit consists of 7.6 m (25') of 

insulated UL/ULC Listed Class 1 air duct and two 0.10 m 
(4") steel band clamps. The duct incorporates a 
corrugated flexible aluminium core, surrounded by 
fibreglass insulation and a vinyl vapour barrier. 

 

CAUTION 

The CAS-2B does not turn the furnace installation 
into a direct vent system. Therefore, the building 
structure must provide for adequate combustion air 
to be delivered 

to the Vacuum Relief Valve. 

The 

burner will need to draw combustion air from the 
VRV’s surroundings if the intake ever becomes 
blocked. Therefore, non-direct vent installation 
codes must be followed. 

 

 

Comprehensive installation instructions are provided with 
the kit. 

 

Outdoor combustion air – side-wall venting, DV-
2000™ 

 

The DV-2000™ venting system is a sealed system and 
completely isolates the furnace from the interior of the 
building. The burner is totally unaffected by any pressure 
fluctuations within the building which makes it ideal for 
tight home construction. 

 

The DV-2000 ™ venting system requires additional parts, 
which are not included with the kit. These additional parts 
must be constructed of 3" Schedule 40 PVC, PVC-SWV, 
SDR-26,SDR-21, Septic Sewer Pipe, or ABS plastic pipe, 
fittings and sealant. Also, installation procedures, piping 
and fittings must conform to the following ANSI /ASTM 
standards: 

 

PVC ASTM 

D-1785 

SDR26, SDR21 

ASTM D-2241 

Septic Sewer Pipe 

ASTM D-2729 

PVC-DWV ASTM 

D-2665 

PVC Primer and Solvent Cement 

ASTM D-2564 

ABS Pipe and Fittings ASTM 

D-2235 

Procedure for Cementing Joints 

ASTM D-2855 

Additional parts required (not included in VTK kit) 

 

a.  3" elbow fitting as required; 
b.  3" plastic pipe; 
c. 

3" - 90° elbow, female-female(for terminal); 

d.  3" female to 2” reducer (Riello 40-BF burner only); 
e.  2".-.90° elbow, street type, female-male (Riello 40-BF burner 

only); 

f.  3" female-female PVC or ABS coupling (not sewer pipe) 

(Beckett AFII burner only); 

g.  Transition bushings to go from PVC or ABS to ASTM D2729 

Septic Sewer Pipe (if applicable).   

 

If PVC fittings are mixed with ABS fittings, use solvent cement that 
is approved for bonding the two plastics. 

 

Intake pipe length - DV-2000™ 

 

The DV-2000 ™ venting system has been certified for 36 
equivalent meters (120') of 3" intake pipe. Count a 90° elbow as 
3.0 equivalent meters (10') and a 45° elbow as 1.5 equivalent 
meters (5') in the calculation.  

 

For Example: 

 

2 lengths of 1.5 m (5') 

=  3.0 equivalent meters (10')  

1 length of 3.0 m (10')  

=  3.0 equivalent meters (10')  

3 elbows 90° 

=  9.0 equivalent meters (30') 

2 elbows 45° 

=  3.0 equivalent meters (10') 

1 elbow 90°  

=  3.0 equivalent meters (10') 

1 elbow 45° (Riello Burner) =  1.5 equivalent meters (  5') 

 

Total

 

=23.0 equivalent meters (75'), 

which is acceptable. 

 

Intake pipe installation - DV-2000™ 

 

Obtain the necessary additional parts, to complete the installation, 
and start the piping at the burner. If the optional vestibule has been 
installed, remove the appropriate knockouts in the side panels of 
the vestibule. The lower 5" knockout in the right hand panel is used 
for the Beckett AFII burner. The higher 5" knockouts on the right 
and left-hand panels are for right or left connection to the Riello 40-
BF burner. 
 

Beckett AFII burner 

 

Remove the burner intake cover by removing the 3 screws 
securing it in place. Discard the cover and screws. Liberally apply 
silicone around the end of a 3" coupling and fully insert the 
siliconed end into the burner opening. Fasten securely with 3 self-
tapping sheet metal screws. 

 

Riello 40-BF burner 

 

Fully insert the female end of the 2" - 90° street elbow into the 
combustion air fitting on top of the burner. Fasten securely with 3 
self-tapping sheet metal screws. Cement the 2" end of the 3" 
female to the 2” female reducer onto the male end of the 2" - 90° 
street elbow. If these parts are not easily obtained, use a 3" - 90° 
street elbow with the male end fitted over the combustion air fitting. 
The fitting will have to be silicone sealed as the fit is a bit loose. 
Fasten securely with 3 self-tapping sheet metal screws.  

 

Terminal connection 

 

Insert the 3" - 90° female-female elbow onto the stainless steel air 
intake fitting located on the right side of the vent terminal (viewed 
from the rear). Fasten securely with 3 self-tapping sheet metal 
screws.  

13 

Summary of Contents for NOLF105A12D

Page 1: ...FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Pr...

Page 2: ...ith the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death bodily injury and or property damage WARNING Fire hazard The furnace...

Page 3: ...hen the furnace is side wall vented CAUTION Do not use any commercially available soot remover This furnace has a ceramic fibre type of combustion chamber Normal servicing of this unit does not requir...

Page 4: ...maximum efficiency and without the use of a side wall power vent The unit will operate at a positive overfire draft and flue draft 1 4 2 Chimney installations When set up for chimney venting this furn...

Page 5: ...all and the terminal is designed to fit through a minimum 2 x 8 joist space c Incorporates a vent blockage safety shutdown system If the vent or intake opening ever becomes partially or fully blocked...

Page 6: ...ion 6 7 3 4 of the NFPA 31 CAUTION Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances even if all other code requirem...

Page 7: ...ER SLEEVE BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 DRIVE THREE STAINLESS STEEL SCREWS STARTING NEAR TOP FIGURE 1 5 FIGURE 1 6 8...

Page 8: ...RE 1 7 FIGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 APPLY THE SEALANT TO THE TUBE END 9 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH SEALANT OUTF...

Page 9: ...EEVE TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL...

Page 10: ...to expose the corrugated stainless steel core 4 Cut the corrugated stainless steel core back by 76 mm 3 on the IFV Series vent You should now have about 76 mm 3 of insulation hanging out past the stai...

Page 11: ...sult in death or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate...

Page 12: ...and Solvent Cement ASTM D 2564 ABS Pipe and Fittings ASTM D 2235 Procedure for Cementing Joints ASTM D 2855 Additional parts required not included in VTK kit a 3 elbow fitting as required b 3 plastic...

Page 13: ...d a Remove drawer assembly or air tube combination b Install nozzle see specifications c Confirm electrode settings d Make the electrical connections e Complete oil line connections CAUTION Do not tur...

Page 14: ...5 Amp maximum to an Electronic Air Cleaner EAC Power will be available to the EAC at all times so it must incorporate a flow proving switch if it is to be wired into the furnace control box Most mode...

Page 15: ...t purges the combustion chamber and vent for a pre set time 15 seconds The ignition transformer also continues to spark for this time period 10 During the post purge cycle the Fan Limit Control cools...

Page 16: ...he blockage still exists the thermostat is again opened and the burner post purges again The post purge function thus becomes an inherent anti short cycling device 4 The unit will essentially go into...

Page 17: ...n air temperature from the supply air temperature 5 If the temperature rise exceeds the temperature specified in Tables 4 1 to 4 3 change to the next higher blower speed tap until the temperature rise...

Page 18: ...Smoke Test and allow for the 1 5 CO2 operating play required by the instructions 5 If the burner still does not shut down before a 1 smoke occurs check for a blockage of the pressure hose or at the h...

Page 19: ...ever if you notice scaling in the radiator you should remove it The wrap around radiator can now be cleaned entirely from the front inspection port The furnace also has external clean out ports so the...

Page 20: ...gn matter from the retention head and electrodes If a Beckett AFG burner has been installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one...

Page 21: ...elephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambie...

Page 22: ...Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0 85 70B 1 00 70B Pump pressure PSIG 130 140 160 130 130 130 Combustion air adjustment screw dial or dial only 3...

Page 23: ...From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 82 2 81 5 80 3 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0...

Page 24: ...m ASHRAE103 standard and US regulation 81 5 81 0 81 0 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W Pump pressure PSIG 130 140 160...

Page 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...

Page 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...

Page 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...

Page 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...

Page 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...

Page 30: ...COMPONENTS AND REPLACEMENT PARTS 31...

Page 31: ...PARTS LIST Model OLR105A12D B50031 B 32...

Page 32: ...pplication 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B30808 01 Electrical box cover 31 B30828 Electrical box box only 32 L07F003 Rocker switch SPST consta...

Page 33: ...PARTS LIST Model OLR160B20C B50032 C 34...

Page 34: ...e panel assembly 30 B30686 01 Right side panel insulation 31 B30668 01 Right bottom filter support 32 B30835 Right top filter support 33 B30782 01 Front panel assembly labels included without logo 34...

Page 35: ...PARTS LIST Model OUF105A12C B50033 B 36...

Page 36: ...r 23 F07O001 Hexagonal flange nut 3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 F06F005 Washer 3 8 AA zinc 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H00...

Page 37: ...PARTS LIST Model OUF160B18C B50034 D 38...

Page 38: ...nt panel assembly labels included 29 B30779 Front panel insulation 30 B30651 Blower door assembly labels included without logo 31 Z99F050 Door handle 32 F06F005 Washer 3 8 AA zinc 33 F07F024 Hexagonal...

Page 39: ...PARTS LIST Model OLF105A12C B50035 B 40...

Page 40: ...61 Sight glass 27 F07O001 Hexagonal flange nut 3 8 16NC brass 28A B30459 5 breech plate chimney application 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B308...

Page 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...

Page 42: ...ech plate direct vent application 28 B30415 02 Gasket heat exchanger 29 B30808 01 Electrical box cover 30 B30826 Electrical box box only 31 L07F003 Rocker switch SPST constant blower operation 32 R02I...

Page 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...

Page 44: ...3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 Z99F050 Door handle 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H009 Relay SPDT 24VAC 29 L01F009 Transforme...

Reviews: