TECHNICAL SUPPORT MANUAL
Split System Heat Pump: N4H3
428 04 510201
3
R--410A QUICK REFERENCE GUIDE
•
R--410A refrigerant operates at 50% -- 70% higher pressures than R--22. Be sure that servicing equipment and
replacement components are designed to operate with R--410A.
•
R--410A refrigerant cylinders are rose colored.
•
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
•
R--410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose when charging into suction line with compressor operating.
•
Manifold sets should be 750 psig high--side and 200 psig low--side with 520 psig low--side retard.
•
Use hoses with 750 psig service pressure rating.
•
Leak detectors should be designed to detect HFC refrigerant.
•
R--410A, as with other HFC refrigerants, is only compatible with POE oils.
•
Vacuum pumps will not remove moisture from oil.
•
Do not use liquid line filter--driers with rated working pressures less than 600 psig.
•
Do not install a suction line filter--drier in liquid line.
•
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•
POE oils may cause damage to certain plastics and roofing materials.
•
Wrap all filter--driers and service valves with wet cloth when brazing.
•
A liquid line filter--drier is required on every unit.
•
Do not use with an R--22 TXV.
•
If indoor unit is equipped with an R--22 TXV, it must be changed to an R--410A TXV.
•
Never open system to atmosphere while it is under a vacuum.
•
When system must be opened for service, break vacuum with dry nitrogen and replace all filter--driers. Evacuate
to 500 microns before recharging.
•
Do not vent R--410A into the atmosphere.
•
Do not use capillary tube indoor coils.
•
Observe all
WARNINGS
,
CAUTIONS, NOTES,
and
bold
text.
International Comfort Products, LLC
Lewisburg, TN 37091 USA