![ICP *9MPT050F12 Installation Instruction Download Page 36](http://html1.mh-extra.com/html/icp/9mpt050f12/9mpt050f12_installation-instruction_613814036.webp)
440 01 2021 01
36
furnace will automatically shift to the high Heat mode for the re-
maining duration of the heating cycle.
For
2--stage
thermostat installations, the R, W1 and W2 wires
from the thermostat connect to the R, W1 and W2 connections on
the furnace control. Set TT Dip switch (SW1--3) to ON position.
During operation, the furnace will shift from Low Heat to high Heat
as requested by the thermostat.
Set thermostat heat anticipator in accordance with the
Technical
Support Manual
.
Heat anticipator setting will need to be measured if 24VAC humidi-
fier is installed. Measure currentin series from R to W1 at the ther-
mostat. Be sure 24VAC humidifier is wired up to control. Allow
furnace to operate for 2 minutes before recording the AC amper-
age reading. Set anticipator on thermostat to recorded value.
Thermostat location has an important effect on the operation of the
furnace. Follow instructions included with thermostat for correct
mounting and wiring.
Low voltage connections to furnace must be made on terminal
board to furnace control. (See
Figure 39
)
If cooling is used, the
Y and G
from the thermostat must be con-
nected to the control board
Y and G
to energize cooling blower
speed.
Optional Equipment
All wiring from furnace to optional equipment
MUST
conform to lo-
cal codes or, in the absence of local codes with the latest edition of
The National Electric Code, ANSI NFPA 70 and/or The Canadian
Electric Code CSA C22.1. Install wiring in accordance with
manufacturer’s instructions. The wiring
MUST
have a minimum
temperature rating of 105
°
C. codes or, in the absence of local
codes, the applicable national codes. Install wiring in accordance
with manufacturer’s instructions.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner
connection.
!
REDUCED FURNACE LIFE HAZARD
Failure to follow caution may result in reduced
furnace life.
Do NOT exceed 115V/1.0 amp. maximum current
load for both the EAC terminal and the HUM
terminal combined.
CAUTION
HUMIDIFIER -- The HUM (115) is energized when the pressure
switch closes on a call for heat. The HUM is energized when
the inducer is energized.
ELECTRONIC AIR CLEANER -- EAC is energized when there
is a blower speed call, except is NOT energized when blower
operates in the hard--wired continuous fan mode.
Furnace Control
The furnace control is preset at the factory with a fixed blower
ON
delay of 30 seconds in the heating mode. The blower
OFF
timing is
preset at 140 seconds. If desired, the fan
OFF
delay can be reset to
obtain the longest delay times while still maintaining comfort lev-
els. See “Furnace Wiring Diagram”.
Dehumidification -- Variable Speed ONLY (*9MPV)
The furnace control is wired for 24 VAC normally--open (N/O) de-
humidistat connection. Connect dehumidistat to the
Y
terminal
and the
1
/
4
²
male quick connect
Dehum
terminal on the furnace
control (See
Figure 39
and
“Furnace Wiring Diagram”.
) A 20% re-
duction of cooling airflow will occur when the
Dehum
dehumidistat
terminal is energized by being connected to
Y
during a call for cool-
ing from the thermostat.
W2
Low Voltage
Terminal Board
W2
Figure 38
Electrical Connections
NOTE: Junction Box can be mounted to either the left or right side.
25--24--78a
NOTE: 115 VAC/60Hz/single--phase
Operating voltage range*: 127 VAC max, 104 VAC min.
* Permissible limits of voltage at which unit will operate satisfactorily
Connection
Box
NE
UT
.
HO
T
Ground
115V. 60 Hz.
W
BK
G
R
C
W1
R
W
R
R
W1
W1
Y
Y
G
G
Single Stage
Thermostat
G
G
Low Voltage
Terminal Board
Two Stage
Thermostat
W2
Furnace Control Fuse
The 24V circuit contains a 5--amp, automotive--type fuse located
on furnace control board. (See
Figure 39
) Any electrical shorts of
24V wiring during installation, service, or maintenance may cause
fuse to blow. If fuse replacement is required, use only a fuse of
identical size (5 amp.)
Summary of Contents for *9MPT050F12
Page 48: ...440 01 2021 01 48 ...