c. Read multiple input discretes (1xxxx)  for DI 

 

 
d. Read multiple input registers (3xxxx) for AI 

 

 
e. Read multiple registers (4xxxx) for AO 

 

 
f. Write multiple registers (4xxxx)  for AO 

 

WF-2026 IO Address Mapping 

 

Table 2: 

(3xxxx) AI address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

30001 

1~5 

Analog Input 

-32768 ~ +32767 (Bipolar) 

0 ~ +65535 (Unipolar) 

 

Table 3: 

(4xxxx) AO address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

40001 

1~2 

Analog Output 

-32768 ~ +32767 (Bipolar) 

0 ~ +65535 (Unipolar) 

R/W 

 

Table 4: 

(0xxxx) DO address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

00001 

1~3

 

Digital Output 

0=OFF, 1=ON 

R/W 

 

Table 5: 

(1xxxx) DI address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

10001 

1~2

 

Digital Input 

0=OFF, 1=ON 

Summary of Contents for WF-2026

Page 1: ...Antenna 2 4GHz 5 dBi ANT 124 05 Note 1 If any of these items are missed or damaged contact the local distributors for more information Save the shipping materials and cartons in case you want to ship...

Page 2: ...Connector Power Signal connector Pin Assignment Description F G Frame Ground Vs 10 30 VDC GND Power RS 232 GND RxD RS 232 RxD TxD RS 232 TxD Table 2 Operating Mode Selector Switch Operating Mode Selec...

Page 3: ...WF 2026 Quick Start RevB1 0 2016 09 3 8 Hardware Connection Power and Serial port connection Figure 4 Power and Serial port wire connection I O connection Figure 5 Wire connections...

Page 4: ...r WF 2000 series will be in the operation mode Step 2 Serial port connection WF 2000 series supports RS 232 serial communication The circuit configuration is as shown in Figure 4 If you do not need pa...

Page 5: ...ryption Key Here does not have the setting 09 Wireless CH Wi Fi connection channel settings Here set to 2 10 Upload parameters After completing the settings above select the RS 232 interface communica...

Page 6: ...for DO FC2 Read multiple input discrete 1xxxx for DI FC3 Read multiple registers 4xxxx for AO FC4 Read multiple input registers 3xxxx for AI FC15 Force multiple coils 0xxxx for DO FC16 Write multiple...

Page 7: ...Points Descriptions Range Access Type 30001 1 5 Analog Input 32768 32767 Bipolar 0 65535 Unipolar R Table 3 4xxxx AO address Begin Address Points Descriptions Range Access Type 40001 1 2 Analog Outpu...

Page 8: ...tion is established successfully 2 Make sure the network configuration is good TCP IP Port Local IP Net Mask 4 How to restore factory default 1 Power on the WF 2000 series I O module 2 Change the Dip...

Reviews: