WF-2026 Quick Start RevB1.0 2016/09
7/8
c. Read multiple input discretes (1xxxx) for DI
d. Read multiple input registers (3xxxx) for AI
e. Read multiple registers (4xxxx) for AO
f. Write multiple registers (4xxxx) for AO
WF-2026 IO Address Mapping
Table 2:
(3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~5
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
Table 3:
(4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40001
1~2
Analog Output
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R/W
Table 4:
(0xxxx) DO address
Begin Address
Points
Descriptions
Range
Access Type
00001
1~3
Digital Output
0=OFF, 1=ON
R/W
Table 5:
(1xxxx) DI address
Begin Address
Points
Descriptions
Range
Access Type
10001
1~2
Digital Input
0=OFF, 1=ON
R