Table 5-2: Supports Function Codes of WF-2000 series

 

Function Code 

Descriptions 

01 (0x01) 

Read Coil Status 

02 (0x02) 

Read Input Status 

03 (0x03) 

Read Holding Registers 

04 (0x04) 

Read Input Registers 

05 (0x05) 

Force Single Coil 

15 (0x0F) 

Force Multiple Coils 

16 (0x10) 

Preset Multiple Registers 

 
Any  other  function  code  request  will  be  returned  with  an  error 

response  indicating  the  function  code  is  not  supported,  as  well  as  a 
request for too much data or data at a register address that not present. 

 

5.2.3

  Data 

 

The data field of Modbus request sent from a client to server devices 

contains  additional  information  that  the  server  uses  to  take  the  action 
defined  by  the  function  code.  This  can  include  items  like  discrete  and 
register addresses, the quantity of items to be handled, and the count of 
actual data bytes in the field. 

 
The data field may be nonexistent (of zero length) in certain kinds of 

requests;  in  this  case  the  server  does  not  require  any  additional 
information. The function code alone specifies the action. 

5.2.4

  Response 

 

If  no  error  occurs  related  to  the  Modbus  function  requested  in  a 

properly  received  Modbus  PDU  (Protocol  Data  Unit)  the  data  field  of  a 
Modbus response from a server to a client contains the data requested. 
If  an  error  related  to  the  Modbus  function  requested  occurs,  the  field 

Summary of Contents for WF-2019/S

Page 1: ...WF 2000 Series AIO User s Manual Ver 1 1 Mar 2014 1 AIO User s Manual www icpdas com WF 2000 Series Wi Fi I O Module...

Page 2: ...any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for its use or for any infringements of patents or...

Page 3: ...2 5 1 Watchdog Timer Settings 18 2 5 2 AI Settings 18 2 6 FW OP Dip switch 19 2 6 1 Firmware Update Mode 19 2 6 2 Firmware Operation Mode 21 3 Software 23 3 1 WF 2000 I O Utility v2 0 or later 23 3 1...

Page 4: ...sponse 39 5 2 5 Data Encoding 40 5 3 Address Mapping 41 5 3 1 WF 2017 I O Address Mapping 41 5 3 2 WF 2019 I O Address Mapping 42 6 Troubleshooting 43 Appendix A 45 A 1 Analog Input Type and Data Form...

Page 5: ...encryption configuration which makes perfect integration to SCADA software and offer easy and safe access for users from anytime and anywhere Figure 1 1 Application architecture for the WF 2000 series...

Page 6: ...communicate directly with each other without the need for a wireless access point Infrastructure mode is the more common network configuration where all wireless hosts clients connect to the wireless...

Page 7: ...the software 1 3 Specifications Table 1 1 System Specifications Modules WF 2017 WF 2019 Wi Fi Interface Antenna 5 dBi Omni Directional Output Power 8 dBm 11Mbps Receive Sensitivity 83 dBm 11Mbps Stand...

Page 8: ...Selectable Resolution 16 bit Accuracy 0 1 FSR Sampling Rate 10 Hz Total Zero Drift 20 V C Span Drift 25 ppm Common Mode Rejection 86 dB Min Normal Mode Rejection 100 dB Input Impedance 2 M 1 M Overvo...

Page 9: ...ired Input Type Thermocouple J K T E R S B N C Resolution 16 bit Accuracy 0 1 FSR Sampling Rate 10 Hz Total Zero Drift 20 V C Span Drift 25 ppm Common Mode Rejection 86 dB Min Normal Mode Rejection 10...

Page 10: ...nual Ver 1 1 Mar 2014 10 2 Hardware 2 1 Front Panel The WF 2000 AIO front panel contains the antenna I O connectors and LEDs Figure 2 1 Front Panel of the WF 2000 AIO RP SMA Connector I O Connector Sy...

Page 11: ...1 second flashes twice per 100 ms Wi Fi unable to connect error Blink per 1000 ms Wi Fi network configurations error Every 1 second flashes three times per 100 ms PWR Power failure Off Data transmiss...

Page 12: ...WF 2000 Series AIO User s Manual Ver 1 1 Mar 2014 12 2 1 2 2 WF 2019 Figure 2 3 I O Connector of WF 2019 Figure 2 4 Pin Assignment of DB 1820...

Page 13: ...switch to the OP position after the upgrade is complete OP mode Firmware operation mode In the WF 2000 the switch is always in the OP position Only when updating the WF 2000 firmware the switch can be...

Page 14: ...Dimensions The diagrams below provide the dimensions of the WF 2000 to use in defining your enclosure specifications All dimensions are in millimeters Figure 2 6 Front Left Side dimension of the WF 2...

Page 15: ...WF 2000 Series AIO User s Manual Ver 1 1 Mar 2014 15 Figure 2 8 Top Bottom dimension of the WF 2017 Figure 2 9 Top Bottom dimension of the WF 2019...

Page 16: ...ection 2 4 1 Power and Serial port connection The following figures describe the Power and the COM port to a serial device via serial network Figure 2 10 Power and Serial port wire connection 2 4 2 I...

Page 17: ...WF 2000 Series AIO User s Manual Ver 1 1 Mar 2014 17 2 4 2 2 WF 2019 Figure 2 12 AI wire connection of WF 2019...

Page 18: ...eries module supplies a jumper for users to active the watchdog timer or not If users want to use this WDT can open the WF 2000 cover and use the Jumper to activate the WDT built in the module as the...

Page 19: ...show how to use this dip switch 2 6 1 Firmware Update Mode Please set the dip switch to the FW position as Figure 2 7 and then the WF 2000 series will work in the Firmware Update Mode after reset the...

Page 20: ...ecute Firmware_Update_Tool exe and follow the below steps to complete the firmware updating process 1 Choose COM interface and COM Port 2 Click Browser button to choose firmware file e g WF20xx fw 3 C...

Page 21: ...Tool program can be downloaded from ftp ftp icpdas com pub cd usbcd napdos wifi io wf 20xx software tool 2 6 2 Firmware Operation Mode In the operation mode users need to set the dip switch to the OP...

Page 22: ...WF 2000 Series AIO User s Manual Ver 1 1 Mar 2014 22 Figure 2 22 OP Position of Dip Switch...

Page 23: ...0 is required You can download this program fromftp ftp icpdas com pub cd usbcd napdos wifi io wf 2019 software utility 3 1 WF 2000 I O Utility v2 0 or later The following is the main screens provided...

Page 24: ...on Configuration This function can enter the basic wireless configuration interface as shown in Figure 3 2 3 Search List Search list provides each item that scans from UDP and display the related info...

Page 25: ...ain the network settings from the DHCP server when the DHCP function is enabled Ad Hoc mode don t support DHCP configuration IP Address WF 2000 IP setting Default 192 168 255 1 Subnet Mask WF 2000 Net...

Page 26: ...be 10 characters WEP 128 Key length must be 26 characters WPA Key length must between 8 64 characters WPA2 Key length must between 8 64 characters Characters of key should be in range of 0 9 or A F or...

Page 27: ...no data exchange within 60 sec the socket will be closed automatically when the this function is enabled Communication Net ID Modbus Net ID of WF 2000 Parameter Transmission Interface The parameter t...

Page 28: ...l items in this form will be introduced in this section Polling Interval This value is the period to poll data to the WF 2000 I O module Note The valid value is 100 5000ms Show Hex Converting the I O...

Page 29: ...lected channel will show in I O configuration region Configuration Region All I O related configurations can be set in this region This region is divided into two parts channel and module related sett...

Page 30: ...ise filter Two filters 50Hz and 60Hz are provided to remove noise generated from power source Wire Detection Enable Disable the open wire detection for thermocouple CJC Enable Enable Disable the CJC C...

Page 31: ...hardware configuration the steps described as follows Step 1 Checking the WF 2000 series firmware operation mode It needs to set the DIP switch to the OP position operating mode as resetting the powe...

Page 32: ...255 0 04 Gateway Gateway settings Here set to 192 168 255 254 05 Wi Fi Mode Wireless network connection mode settings Here set to Ad Hoc mode If the mode is AP mode wireless AP devices is needed 06 SS...

Page 33: ...IP Setting a Open Network connections and entry the properties setting of wireless network connections Figure 4 4 Properties setting of wireless network connections b Select the Internet Protocol TCP...

Page 34: ...192 168 255 10 Subnet mask as 255 255 255 0 Finally press OK button Figure 4 6 IP address setting interface 02 Wireless network connection a View available wireless networks and you can see the WF 20...

Page 35: ...ppear connection success screen Figure 4 9 Connection successful interface 4 2 3 Access I O data 01 Connection with WF 2000 I O utility v2 0 or later a Open WF 2000 I O utility and click the Search bu...

Page 36: ...nterface 02 Connection with Modbus TCP utility a Open Modbus TCP utility and key in the IP address as 192 168 255 1 Port as 502 Finally click the Connect button b If the network settings are correct t...

Page 37: ...ode Wizcon Wonderware etc 5 1 What is Modbus TCP IP Modbus is a communication protocol developed by Modicon in 1979 Different versions of Modbus used today include Modbus RTU based on serial communica...

Page 38: ...le 5 1 MODBUS Application Protocol Header Fields Length Description Transaction Identifier 2 bytes Identification of Request Response transaction Copied from request to response Protocol Identifier 2...

Page 39: ...Modbus request sent from a client to server devices contains additional information that the server uses to take the action defined by the function code This can include items like discrete and regist...

Page 40: ...al function code from the request PDU with its most significant bit set to logic 1 5 2 5 Data Encoding Modbus uses a big endian representation for address and data items This means that when a numeric...

Page 41: ...at a time therefore each of these data items will fit within one register that is read Table 5 4 A 16 bits word item Value 1st 2nd 0x1234 0x12 0x34 5 3 Address Mapping 5 3 1 WF 2017 I O Address Mappi...

Page 42: ...x AI address Begin Address Points Descriptions Range Access Type 30001 0x0 0 9 Analog Input 32768 32767 R 30010 0xA 1 CJC data 32768 32767 R Table 5 7 4xxxx AO address Begin Address Points Description...

Page 43: ...al quality 3 TCP connection can not be established 1 Make sure WLAN connection is established successfully 2 Make sure the network configuration is good TCP IP Port Local IP Net Mask 4 How to restore...

Page 44: ...ET Framework v4 0 installed as well or not Users can install NET Framework v4 0 in the following website Microsoft NET Framework 4 Web Installer http www microsoft com en us download details aspx id 1...

Page 45: ...ring Unit 100 100 02h 100 100 mV 2 s comp HEX 7FFFh 8000h Engineering Unit 500 500 03h 500 500 mV 2 s comp HEX 7FFFh 8000h Engineering Unit 1 1 04h 1 1 V 2 s comp HEX 7FFFh 8000h Engineering Unit 2 5...

Page 46: ...mocouple 210 760 C 2 s comp HEX 7FFFh DCA2h Engineering Unit 1372 270 0Fh Type K Thermocouple 270 1372 C 2 s comp HEX 7FFFh E6D0h Engineering Unit 400 270 10h Type T Thermocouple 270 400 C 2 s comp HE...

Page 47: ...ype C Thermocouple 0 2320 C 2 s comp HEX 7FFFh 0000h Engineering Unit 20 0 1Ah 0 20 mA 2 s comp HEX FFFFh 0000h Note Getting the 7FFFh value in all of the thermocouple type codes it means that the the...

Reviews: