USB-87P1/2/4/8 User Manual, version: 1.4
59
(Error)
Configuration
failed
The configured commands are wrong for
DCON Protocol.
2. Click the "Write To 87Pn" button to write the settings to
87Pn CPU again.
06H
Bright
(Error)
Cannot find
module
The configured module at this slot has been
removed. It is empty now.
1. Please insert a correct module as previous configured
one.
2. Or configure with DCON Utility as "Empty" and click the
"Write To 87Pn" button to write the configuration to
87Pn CPU.
07H
Bright
(Error)
Incorrect
module name
Configure failure:
The insert & configure module name are different, insert
the correct one or run the Dcon Utility to modify the
settings accord with the module name.
The module inserted in this slot is not the
same as previous configured.
08H
Bright
(Error
)
Internal INIT*
pin failed
Configure failure:
1. Please restart the power to initialize to I/O module
2. If it still failed to initialize, send it back to factory to
check.
Note: USB-87Pn only supports high profile 87K I/O
modules.
The INIT Pin is failed to connect with the
GND and module failed to initialize.
09H
Bright
(Error
)
Module
address over
255 (FFh)
The module address is over 255 (FFh).
The maximum address of
87P1 is 254 (FEh)
87P2 is 253 (FDh)
87P4 is 251 (FBh)
87P8 is 247 (F7h)
0AH
Bright
(Error
)
The command
count saved to
87Pn is not the
same as DCON
Utility
This error might be caused by following
reasons.
1. Command length error.
2. Command checksum error.
3. Communication error during the process
of writing commands to 87Pn.
Please configure this 87K I/O module with DCON Utility,
and click the "Write To 87Pn" button to write the
configuration to 87Pn CPU again.