Read Cache (ms)
When sharing Modbus RTU/ASCII device/data between several
master devices, the read-cache function can be used to reduce the
loading on the serial communication and ensure faster TCP
responses.
Valid range: 10, 20 to 65530 (ms)
Disable = 0
Virtual Modbus ID
This parameter is used to skip the Modbus messages when Modbus
ID of slave device is NOT in the specified range.
Available ID range: 0 to 255
Modbus ID Offset
This parameter is used to set the Modbus ID offset.
For example:
Virtual ID = 1 to 10, offset = 10, then physical Slave ID = 11 to 20.
Virtual ID = 31 to 40, offset = -10, then physical Slave ID = 21 to 30.
Available offset range: -255 to 255
No change =0 (Default)
Submit
Click this button to save the revised settings to the tSH-700.