Indicator LED   

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

PISO-DNS100U Quick Start Manual (Version 1.0, Jan/2010)    ------------ 

 

Green 

LED 

Red 

LED 

Event or Status Description 

1 OFF  ON 

There are some problems with the hardware of the PISO-DNS100U 
board. Please contact your local field agent. 

2 OFF Twinkle 

There are some slaves which can not be on-line. There exists at least 
one duplicate MAC ID in the DeviceNet network. 

3 ON  OFF 

This indicates that the firmware is working. All slave devices in the 
PISO-DNS100U are communicating with the master successfully. 

4 ON  ON 

This indicates that the firmware works fine. But there is no any slave 
device configuration inside the EEPROM of the PISO-DNS100U. 

5 Twinkle  OFF 

1.

 

There are slaves which have problems with the communication. 

2.

 

The slaves are on-line and waiting for the request message from 
the master. 

z

 

Hardware Installation 

z

 

Virtual DeviceNet Slaves 

Summary of Contents for PISO-DNS100U

Page 1: ...ould help you quickly to familiarize yourself with the PISO DNS100U PCI board and DeviceNet communication For more the detail information please refer to the user s manual of the PISO DNS100U Here is...

Page 2: ...ed on the commands of exchanging information and I O data To establish slave server mechanism there are four main steps to be followed The figure demonstrates the basic process for the DeviceNet commu...

Page 3: ...the users how to connect the master and slave devices by CAN bus The slave devices should be connected to form the serial type which is shown as follows The following wire connection is wrong which i...

Page 4: ...duplicate MAC ID in the DeviceNet network 3 ON OFF This indicates that the firmware is working All slave devices in the PISO DNS100U are communicating with the master successfully 4 ON ON This indicat...

Page 5: ...ftware in the path of devicenet slave piso dns100 in the Fieldbus_CD or from ftp ftp icpdas com tw pub cd fieldbus_cd devicenet slave piso dns100 After installing the software the related software dem...

Page 6: ...ich the users have set Please click the ActiveBoard button to active the specific board which you have selected in the Board No field 4 Pressing Add Device button to add the slave into the EEPROM It p...

Page 7: ...n the Devices in EEPROM field PISO DNS100U Quick Start Manual Version 1 0 Jan 2010 7 8 Please click ActiveBoard button to active the specific board which you have selected in the Board ID field Note t...

Page 8: ...ws the output value which was sent by the master device at the output filed It means that the master can exchange the I O data with the slave device 11 After communicating with the master device the u...

Reviews: