Programmable Serial-to-Ethernet Device Server
PDS Series User Manual, Version 2.5, Mar. 2019
-
85 -
Item
Description
Default
Web Server
This parameter is used to enable or disable Web Server
function.
If the web server has been disabled (Web Server=0), refer to
FAQ:
“How to enable web server for the PDS/7188EN Series
0 = Disabled, 1 = Enabled
1
Telnet Server
This parameter is used to enable or disable Telnet Server
function.
0 = Disabled, 1 = Enabled
1
Ping Gateway at start
If the setting is 1 (enabled), the PDS series will send a ping
packet to the gateway during the power-on stage. It is used to
inform the gateway that a PDS series (itself) has joined the
network.
0 = Disabled, 1 = Enabled
0
(Disabled)
TCP ACK Delay (ms)
PDS series does not want to send an empty ACK followed by a
TCP data packet 1ms later, every time. So it delays a little (TCP
ACK Delay), and then can combine the ACK and data packet
into one. This efficiency reduces the number of packets and
reduces network loadings.
50 ms
Broadcast
This parameter is used to receive or reject UDP broadcast
packets.
1 = receive UDP broadcast packets
0 = reject UDP broadcast packets
1
Connection WDT timeout
(ms)
If the PDS series does not receive any data from a client PC
within the period of the “Connection WDT timeout”, the
module will close the connection to the client.
0 = Disabled,
Min. setting value = 10000
0
(Disabled)