M-2004 & M-7004 User Manual, v 1.0.2, Apr. 2020 E-mail: [email protected]
Copyright © 2017 ICP DAS Co., Ltd. All Rights Reserved.
39
Address
Description
Attribute
31313 ~
31392
41313 ~
41392
Serial number of removed sensors of port 0, 4
registers for a sensor
R
00001 ~
00004
Write 1 to rescan sensors on a port for port 0 to
3.
W
00033 ~
00052
Write 1 to remove the channel index of a
sensor for port 0
W
00053 ~
00072
Write 1 to remove the channel index of a
sensor for port 1
W
00073 ~
00092
Write 1 to remove the channel index of a
sensor for port 2
W
00093 ~
00112
Write 1 to remove the channel index of a
sensor for port 3
W
00129 ~
00132
Write 1 to clear all high latched temperature
readings of a port for port 0 to 3
W
00161 ~
00164
Write 1 to clear all low latched temperature
readings of a port for port 0 to 3
W
00257
RS-485 Protocol, 0: DCON, 1: Modbus RTU
Only for Modbus RTU protocol
R/W
00260
Modbus RTU host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear host
watchdog timeout status
Only for Modbus RTU protocol
R/W
00261
RS-485 host watchdog mode, 1: enable, 0:
disable.
Only for Modbus RTU protocol
R/W
00270
Host watch dog timeout status, write 1 to clear
host watch dog timeout status
Only for Modbus RTU protocol
R/W