![background image](http://html.mh-extra.com/html/icp-das-usa/m-2004/m-2004_user-manual_614685033.webp)
M-2004 & M-7004 User Manual, v 1.0.2, Apr. 2020 E-mail: [email protected]
Copyright © 2017 ICP DAS Co., Ltd. All Rights Reserved.
33
Baud Rate Setting (CC)
Bits 5:0
Baud rate, 0x03 ~ 0x0A
Code
0x03
0x04
0x05
0x06
Baud
1200
2400
4800
9600
Code
0x07
0x08
0x09
0x0A
Baud
19200
38400
57600
115200
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bits
10: even parity, 1 stop bit
11: odd parity, 1 stop bit
Data Format Setting (FF)
Bit 6
0: checksum disabled
1: checksum enabled