LC-101H/LC-102H User Manual
-
31 -
Appendix C: DCON Command Sets
Command
Description
$AA0CN
Span calibration of an analog input channel, N is 0 for
LC-101H and 0 or 1 for LC-102H. Span calibration current
is 5A.
$AA1CN
Zero calibration of an analog input channel, N is 0 for
LC-101H and 0 or 1 for LC-102H. Zero calibration current
is 0.1A.
$AA2
read configuration
$AA4
Read the synchronized data that was retrieved by the last
#** command.
response
> SOI0000, S is 1 for the first read and 0 for not the
first read
$AA5
read reset status
!AA1 first after power on, !AA0 others
$AA6
Read the digital output and input status
response
> 0O0I00, where O is digital output and I is digital input
$AAC
Clear the status of the latched digital input and output
channels.
$AACN
Clear the counter value of a digital input channel, N is 0 for
LC-101H and 0 or 1 for LC-102H.
$AAF
read firmware version
$AAI
read INIT status
response:
!AA0 -> INIT short to GND
!AA1 -> else
$AALS
Read the status of the latched digital output and input
channels,
S is 0 to read the low latched status and 1 to read the high
latched status.
response:
!0O0I00
$AALC0h
Specify the dependency of the digital output channel on the
Summary of Contents for LC-101H
Page 1: ...LC 101H LC 102H User Manual 1 LC 101H LC 102H User Manual Version 1 0 0 Date Jul 2022...
Page 5: ...LC 101H LC 102H User Manual 5...
Page 9: ...LC 101H LC 102H User Manual 9 Switch SW2 2 3 Pin Assignments...
Page 10: ...LC 101H LC 102H User Manual 10 2 4 Wire Connections...
Page 11: ...LC 101H LC 102H User Manual 11 2 5 Internal I O Structure...
Page 13: ...LC 101H LC 102H User Manual 13 2 7 Dimensions unit mm...