I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 32
2.8
~
AAAS
Description
: Set counter alarm mode. Refer to Sec. 1.8.2 for more
information.
Syntax
: ~AAAS[chk](cr)
~ is a delimiter character
AA=2-character HEX module address, from 00 to FF
S=0
alarm mode 0.
1
alarm mode 1.
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Response
: valid command
!AA[chk](cr)
invalid command
?AA[chk](cr)
no response
syntax error or communication
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Example
:
command: ~01A0(cr)
response : !01(cr)
command: ~02A1(cr)
response : !02(cr)
Set alarm mode=0.
Set alarm mode=1.
7080/7080D