HRT-711 Modbus TCP to HART Gateway
- QuickStart (Jan/2018)
ICP DAS USA, Inc.
|
www.icpdas-usa.com
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
7
-
Communication test
Step 1: Connect PC, HRT-711 and HART slave device according
to figure1.
Step 2: Swtich the DIP switch to the “Init” position.
Step 3: Turn on the power of the HRT-711.
Step 4: Wait for the “HART” LED indicator to be always on status. If the
led always flashes, please check the HART network wiring. It
means the HRT-711 can’t connect to the HART slave devices.
Step 5: Execute the HRT-711 utility.
Step 6: Click “HART to Modbus”
Step 7: Select HRT-711 and ComPort in the communication settings.