HRT-310 Modbus RTU to HART Gateway
- QuickStart (Aug/2017)
ICP DAS USA, Inc.
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
6
Communication Test
Step 1
: Connect PC, HRT-310 and HART slave device according
to
figure1.
Step 2
: Set the DIP switch of the “Default” to be “ON” position.
Step 3
: Turn on the power of HRT-310.
Step 4
: Wait for the “RUN” LED to be always on status. If the “RUN” LED
always flashes, it means the HRT-310 can’t communicate with
the HART device. Please check the HART network wiring.
Step 5
: Execute the HG_Tool utility.
Step 6
: Set the communication settings between PC and HRT-310.
When the DIP switch of the “Default” to be “ON” position, the HRT-310
will adopt the below comport communication settings.
[1] Protocol: MB RTU
[2] Net ID: 1
[3] Baud Rate: 115200 bps
[4] Data Bits: 8
[5[ Stop Bits: 1
[6] Parity: None
=> So the HG_Tool must have the same settings with the HRT-310 as
shown in the below figure.