ICP DAS USA HRT-310 Quick Start Manual Download Page 4

 

 

HRT-310  Modbus RTU to HART Gateway

 - QuickStart (Aug/2017)  

ICP DAS USA, Inc.

 

www.icpdas-usa.com

 | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

RS-232 Wiring

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

HART network wiring

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for HRT-310

Page 1: ...the Modbus to connect HART devices and converting the HART protocol to Modbus RTU ASCII protocol In addition the gateway is equipped with a more powerful built in resistor allowing connecting up to 15...

Page 2: ...tion LP 12 V of Loop Power 24VDC HART 11 Positive of HART HART 10 Negative of HART VS 23 V of Power Supply 10 30 VDC GND 24 GND of Power Supply RXD 18 Receive Data of RS 232 TXD 17 Transmit Data of RS...

Page 3: ...d Default to be ON position Item ON Resistor Enable HART loop resistor 250 Ohm 1W Default Adapt the default settings Refer to HART network wiring LED Indicator LED Status Description Name PWR ON Modul...

Page 4: ...HRT 310 Modbus RTU to HART Gateway QuickStart Aug 2017 ICP DAS USA Inc www icpdas usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 4 RS 232 Wiring HART network wiring...

Page 5: ...above must be installed first If the NET Framework 2 0 or above exists in the PC please omit the step Install HG_Tool exe 1 Users can download the HG_Tool from the below source CD_Disk CD hart gateway...

Page 6: ...RUN LED to be always on status If the RUN LED always flashes it means the HRT 310 can t communicate with the HART device Please check the HART network wiring Step 5 Execute the HG_Tool utility Step 6...

Page 7: ...If the traffic light always keeps in the yellow light it means the PC can t connect to HRT 710 please check the RS 232 wiring Step 9 Click the Device Information icon Then select the Default CMD or U...

Reviews: