GT-540P-3GWA-OEM1 user’s manual v1.0
Hold Time
"
. The unit is second.
(Range : 0 ~ 65535 sec)
DO Channel
The text will define which DO channel will
output according to the DI triggering.
(Channel 0 ~ 1)
DO On Time(sec)
The DO channel would keep outputting
according to this time, when DI channel is
triggered and “DO Off Condition” is “time”.
The unit is second.
(Range : 0 ~ 65535 sec)
DO Off Condition
These conditions of the DO terminating
outputting when DO is output by DI trigger.
1.
Disable: Disable the DO linkage with DI
channel.
2.
Time: The DO output would keeping “ON”
according to the “DO on Time” when DI is
triggered.
3.
Input Status: The DO channel output would
be kept contiguously according to the time
of the “Return Hold Time” when the DI
returns to the non-trigger status
(2)
DO
Item Description
Cycle Time(sec)
The time of a duty cycle for DO.
If it is 0, duty cycle function is disabled.
(Range : 0 ~ 65535 , Unit : Second)
Cycle Percent(%)
The percentage of DO output would keeping
“ON” in a duty cycle.
(Range : 0 ~ 100, Unit : %)
Auto-Stop Time(sec)
If the GT-540P-3GWA-OEM1 disconnect to
RTU Center over this time, the operation of
duty cycle would be stopped automatically.
If it is 0, the GT-540P-3GWA-OEM1 does
not stop the operation of duty cycle
automatically.
(Range : 0 ~ 65535 , Unit : Second)
GT-540P-3GWA-OEM1 user’s manual, Version 1.0, 2013/03