GRP-520 User Manual, V1.30, Aug. 2015
74
4.8
Email or FTP report I/O logger file.
This example shows how to using GRP-520 to report I/O logger file periodically.
(1)
About Modbus configure, please refer
section 4.5
.
(2)
Configure Email / FTP function in “Email/FTP” Tab.
You must set “Data Log Interval”
field more than 0, or log report function will be disabled
. (include FTP and Email)
Configure “Data Log Interval” to record IO data into csv file. (0
disable)
filename format: GRP-520_StationID_YYYYMMDD_hhmmss.csv
ex: GRP-520_13_20140806_172347.csv
Configure “Max. Time per Log File” to indicate how long to change / send back log file.
If the file size is close 3MB, GRP-520 will create a new log file to recode I/O data and
move old log file into “/RTU/LOGFILE/” in SD card.
If you need FTP report function, please set all FTP parameters and set “Enable FTP
Function” as “Enable”. GRP-520 will send log file to FTP Sever when new log file is
available.
If you need Email report function, please set all Email parameters and set “Enable FTP
Function” as “Enable”.
If you need 2 or more contact, please use comma “,” to separate
each contact
.