CAN-Logger series CAN Bus data logger devices User Manual (version 1.0.1)
Page: 25
Copyright © 2015 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
“Defined Baud Rate”:
CAN Bus baudrate used for user-defined. After set the CAN
rotary switch to ‘9’, you can set this parameter to the baud
rate you need.
“Sample Point”:
Sample point of CAN baud rate bit timing.
“CAN ID Filter”:
CAN message ID filter.
[Mode]:
Mode of CAN ID, can be set to 2.0A (11-bit CAN ID) and
2.0B (29-bit CAN ID).
[Mask]:
Mask CAN ID bits. Be use with [Arbitration] parameter.
Bit value of 0 mean does not care the bit of
corresponding “Arbitration CAN ID” and bit value of 1
means this bit need be matched with the corresponding
bit of “Arbitration CAN ID”.
[Arbitration]:
Arbitration CAN ID bit. The CAN ID that you want to
use for the CAN ID filter.
[Example]
1. All CAN ID passed.
[Mode] = “2.0A”
[Mask] = “000”
[Arbitration] = “000”
2. Filter
all
messages except ID of 0x123.
[Mode] = “2.0A”
[Mask] = “7FF”
[Arbitration] = “123”
3. Filter all messages except ID from 0x100 ~ 0x10F.
[Mode] = “2.0A”
[Mask] = “7F0”
[Arbitration] = “100”
[Other Parameters]
“Device Real-time clock”:
RTC time of the CAN-Logger device. This parameter is
used for CAN-Logger device to log the received CAN
messages into SD card.
“RTC Battery Voltage”:
Crrent battery voltage that RTC used. The battery
valtage must be the value between 2.2V
DC
to 3.6V
DC.