5.3 Maintenance menu (since V3.00 firmware)
This menu displays any real time measurement of the protection, as well as the values kept
in memory.
MAIN MENU
MAINTENANCE
Available real time measures
CURRENT I1
0.0 A
Measure of the phase 1 primary
current
0.0 to 65535A
CURRENT I3
0.0 A
Measure of the phase 3 primary
current
0.0 to 65535A
CURRENT Io
0.00 A
Measure of the earth Io primary
current
0.0 to 65535A
FREQUENCY
50.00 Hz
Measure of the network frequency
45 to 55 if Fn = 50 Hz
55 to 65 if Fn = 60 Hz
THERMAL STATE
0.0 %
Measure of the thermal state of motor 0.0 to 500 %
NEGATIVE SEQ.
0.0 %
Measure of the rate of negative
sequence of current
POSITIVE SEQ.
0.0 %
Measure of the rate of positive
sequence of current
LAST START CURR.
0.0 A
Maximum current measured during
last start (firmware 2.xx)
0 to 65535A
LAST START DATE
01/12 01:52:47
Date of last start
Day/Month Hour : Minute : Second
MAX START CURR.
0.0 A
Maximum current measured during all
starts
0 to 65535A
STARTS ALLOWED
4
number of authorized remaining starts Inactive if function MAX
NBR STARTS inactive.