ICAS FIRE PANEL IFP–2.32

IFP-2.32 Manual

1) DESCRIPTION

IFP-2.32

  is  a  microprocessor   controlled  Fire 

Panel with 2 loops intended either for privat 
Homes & Apartments or   larger installations. 
The   two   loops   are   balanced   by  

2k7   Ohm 

resistor

  mounted   at   the   last   detector   in   each 

loop. The device is named as IFP-Y.X, where 
Y describes number of loops and X number of 
detectors in the loop.  

IFP-2.32

  can handle 32 

detectors of standard 12V Icas detectors type 
500-IDx or Icas type  CHOR-E (9V) in each 
loop. 

Connection of Detectors:

-

500-IDx   detectors   have   integrated 
sirene but the sirene are triggered from 
the Fire Panel. A 4 wire solution is used 
to activate the integrated sirene. An external siren can also be used. The siren is con-
trolled by the  

IFP-2.32

 Fire Panel. The alarm relay of 

IFP-2.32

 can be used for extern-

al siren control. 

-

CHOR-E detectors (9V detector) can be connected only “Alarm in one Alarm in all” 
function.

The different functions are chosen by use of jumper.

The IFP-2.32 is supplied by 230V AC and the internal backup 

12V/0,8Ah.

   The IFP-2.32 is 

equipped with one internal siren, fault relay, alarm relay and 2 open collectors, each for one 
loop. The IFP-2.32 is controlled by 4 underlighted pushbuttons. In the IFP-2.32 is possible to 
control each loop separately by the functions for Switch OFF/ON loops, also Switch OFF/ON 
the Test of loops, remove Alarm and Fault in loops. The IFP-2.32 includes also complete 
functions for battery testing and firmware testing. 

When the Alarm is triggered, the internal siren of IFP-2.32 and siren of detectors / External 
sirenes can be silenced with pushbutton SIREN. This will stop the sirens of detectors. Remov-
ing of Alarm and other control functions are described in chapter Button Functions.

___________________________________________________________________________

ICAS AS

[email protected]

www.icas.no

1

Summary of Contents for IFP-2.32

Page 1: ...en control CHOR E detectors 9V detector can be connected only Alarm in one Alarm in all function The different functions are chosen by use of jumper The IFP 2 32 is supplied by 230V AC and the interna...

Page 2: ...r VD 04 shielded cable or equivalent type Shield of the cable has to be terminated in the 0V in all the Detectors and to Shield terminal in the Fire Panel Set all jumpers in correct position Switch th...

Page 3: ...SMOKE DETECTORS CONNECTION CHOR E SMOKE DETECTORS Connection meets EN52 2 with only the exception of clause 8 2 4 Removal of a point JUMPERFIX ________________________________________________________...

Page 4: ...detected when the loop is open or when the loop is shorted If the battery is very low and starts to be undercharged and main power is off the IFP 2 32 is switched off 3 LED SIGNALIZATION Power Dark N...

Page 5: ...evel 2 The actual Loop LED is lightning TEST At least one loop is in test mode Can be switched off on in level 2 Actual Loop LED is flashing OK SIGNALIZATION POWER LED 2x flashes and 2x short beeps Us...

Page 6: ...alarm in loops NOTE The detectors in the loop is not in alarm the current in the loop is lesser than 12 mA 1 First step is entering into LEVEL 2 Press A B at the same time If received OK Signalization...

Page 7: ...t Alarm is entering into LEVEL 2 Press A B at the same time If received OK Signalization occurs step 1 2 Press and hold A B step 2 3 Then hold A B and press 2x B A for Fault Reset Choice in the loop T...

Page 8: ...the loop The control choice can be checked by OFF blinking LED Do not release the button A B The control choice is confirmed by A B Lamp button If received OK Signalization occurs step 3 4 Release Al...

Page 9: ...tch Off On Test Choice of the loop The control choice can be checked by TEST blinking LED Do not release the button A B The control choice is confirmed by A B Lamp button If received OK Signalization...

Page 10: ...x LAMP LOOP B is in Test Off On Choice Button LAMP is used at the end as confirmation of the action 4 Release Buttons FAULT LED is dark 5 LAMP SIREN at the same time or wait 30 s Exit LEVEL 2 and retu...

Page 11: ...LT Reset A 3x pressed B for Switch Off On A 4x pressed B for Switch Test Off On LAMP SIREN Return into LEVEL1 A LAMP for confirmation previous choices A 1x pressed B for ALARM Reset A 2x presed B for...

Page 12: ...oltage 12 V 20 for CHOR E 9 5V 5 OUTPUTS Fault relay 1x 125VAC 0 5A 24VDC 1A Alarm relay 1x 125VAC 0 5A 24VDC 1A Transistor outputs OC 2x 14V 0 1A Power output for external device 12 V 20 5mA 9 5V 5 5...

Page 13: ...4 2007 A2 Control Unit for electrical fire alarm systems for buildings Power Supply for electrical fire alarm systems for buildings IFP 2 32 Optional requirements State Test Documentation IFP 2_32 Man...

Page 14: ...DANCE WITH THE MANUFACTURER S RECOMMENDATION ALWAYS USE SEALED LEAD ACID BATTERIES YUASA NP0 8 12 12V 0 8Ah LOOPS CHECKS Set the TEST function in IFP 2 32 for LOOP A and B For further instruction see...

Reviews: