Thermal grease
The thermal grease must be replaced whenever the heat sink has been removed
from the top of the microprocessor and is going to be reused or when debris is
found in the grease.
To replace damaged or contaminated thermal grease on the microprocessor and
heat exchanger, complete the following steps:
1. Place the heat-sink assembly on a clean work surface.
2. Remove the cleaning pad from its package and unfold it completely.
3. Use the cleaning pad to wipe the thermal grease from the bottom of the heat
exchanger.
Note: Make sure that all of the thermal grease is removed.
4. Use a clean area of the cleaning pad to wipe the thermal grease from the
microprocessor; then, dispose of the cleaning pad after all of the thermal grease
is removed.
Microprocessor
0.02 mL of thermal
grease
5. Use the thermal-grease syringe to place nine uniformly spaced dots of 0.02 mL
each on the top of the microprocessor.
Note: 0.01mL is one tick mark on the syringe. If the grease is properly applied,
approximately half (0.22 mL) of the grease will remain in the syringe.
80
System x3650 M2 Type 7947: Installation and User’s Guide
Summary of Contents for x3650 - System M2 - 7947
Page 1: ......
Page 2: ......
Page 3: ...System x3650 M2 Type 7947 Installation and User s Guide...
Page 8: ...vi System x3650 M2 Type 7947 Installation and User s Guide...
Page 16: ...xiv System x3650 M2 Type 7947 Installation and User s Guide...
Page 38: ...22 System x3650 M2 Type 7947 Installation and User s Guide...
Page 58: ...42 System x3650 M2 Type 7947 Installation and User s Guide...
Page 126: ...110 System x3650 M2 Type 7947 Installation and User s Guide...
Page 146: ...130 System x3650 M2 Type 7947 Installation and User s Guide...
Page 158: ...142 System x3650 M2 Type 7947 Installation and User s Guide...
Page 164: ...148 System x3650 M2 Type 7947 Installation and User s Guide...
Page 165: ......
Page 166: ...Part Number 69Y3926 Printed in USA 1P P N 69Y3926...