Table 8. DSA messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
See Chapter 4, “Parts listing, System x3690 X5 Types 7147, 7148, 7149, and 7192,” on page 249 to determine
which components are customer replaceable units (CRU) and which components are field replaceable units
(FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
Trained service technician.
v
Go to the IBM support Web site at http://www.ibm.com/supportportal/ to check for technical information,
hints, tips, and new device drivers or to submit a request for information.
Message
number
Component Test
State
Description
Action
202-802-xxx
Memory
Memory
Stress Test
Failed
General error:
memory size is
insufficient to
run the test.
1.
Make sure that all memory is enabled by
checking the Available System Memory in
the Resource Utilization section of the
DSA event log. If necessary, enable all
memory in the Setup utility (see “Using
the Setup utility” on page 402).
2.
Make sure that the DSA code is at the
latest level. For the latest level of DSA
code, go to http://www.ibm.com/
support/docview.wss?uid=psg1SERV-
DSA.
3.
Run the test again.
4.
Run the standard memory test to validate
all memory.
5.
If the failure remains, go to the IBM Web
site for more troubleshooting information
at http://www.ibm.com/systems/
support/supportsite.wss/
docdisplay?brandind=5000008
&lndocid=SERV-CALL.
202-901-xxx
Memory
Memory
Stress Test
Failed
Test failure.
1.
Run the standard memory test to validate
all memory.
2.
Make sure that the DSA code is at the
latest level. For the latest level of DSA
code, go to http://www.ibm.com/
support/docview.wss?uid=psg1SERV-
DSA.
3.
Turn off the system and disconnect it
from power.
4.
Reseat the DIMMs.
5.
Reconnect the system to power and turn
on the system.
6.
Run the test again.
7.
If the failure remains, go to the IBM Web
site for more troubleshooting information
at http://www.ibm.com/systems/
support/supportsite.wss/
docdisplay?brandind=5000008
&lndocid=SERV-CALL.
152
System x3690 X5 Types 7147, 7148, 7149, and 7192: Problem Determination and Service Guide
Summary of Contents for System x3690 X5
Page 1: ...System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 8: ...vi System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 13: ...Safety statements Safety xi...
Page 22: ...4 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 266: ...248 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 278: ...260 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 386: ...368 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 407: ...1 2 Chapter 5 Removing and replacing components 389...
Page 444: ...426 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 454: ...436 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 461: ...weight of memory enclosure 28 Index 443...
Page 462: ...444 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 463: ......
Page 464: ...Part Number 47C8865 Printed in USA 1P P N 47C8865...