![IBM System Storage TS3500 Introduction And Planning Manual Download Page 128](http://html1.mh-extra.com/html/ibm/system-storage-ts3500/system-storage-ts3500_introduction-and-planning-manual_4089689128.webp)
Table 37. Clearance requirements for the TS3500 Tape Library
. The table gives the
clearances for a library both with and without service bays.
Number of Active Frames
Length of A in Figure 19 on
page 105 or in Figure 20 on
page 106 (Not Including
Service Bays)
(see Notes 1, 2, and 3)
Length of A in Figure 19 on
page 105 or in Figure 20 on
page 106 (Including Service
Bays)
(see Notes 1 and 2)
1
1 544 mm (60.79 in.)
Not applicable
2
2 298 mm (90.47 in.)
4 569 mm (179.88 in.)
3
3 052 mm (120.16 in.)
5 324 mm (209.61 in.)
4
3 806 mm (149.84 in.)
6 079 mm (239.33 in.)
5
4 560 mm (179.53 in.)
6 833 mm (269.02 in.)
6
5 314 mm (209.21 in.)
7 588 mm (298.74 in.)
7
6 068 mm (238.90 in.)
8 342 mm (328.43 in.)
8
6 822 mm (268.58 in.)
9 097 mm (358.15 in.)
9
7 576 mm (298.27 in.)
9 852 mm (387.87 in.)
10
8 330 mm (327.95 in.)
10 606 mm (417.56 in.)
11
9 084 mm (357.64 in.)
11 361 mm (447.28 in.)
12
9 838 mm (387.32 in.)
12 115 mm (476.97 in.)
13
10 592 mm (417.01 in.)
12 870 mm (506.69 in.)
14
11 346 mm (446.69 in.)
13 625 mm (536.42 in.)
15
12 100 mm (476.38 in.)
14 379 mm (566.10 in.)
16
12 863 mm (506.42 in.)
15 134 mm (595.3 in.)
Note:
1.
For Models L22, D22, L23, D23, L52, D52, L53, D53, S24, S54, and the service bays, the
size of a clearance is measured by its depth from the outside of the frame and its width
along the library. At the ends of the library, the depth of the service clearance is
measured from the front of the library to the rear. In Figure 19 on page 105, B refers to
the distance (2737 mm or 107.8 in.) that is the total service clearance between the front
and the rear of the library.
2.
For Models L32 and D32, the size of a clearance is measured by its depth from the
outside of the frame and its width along the library. At the ends of the library, the
depth of the service clearance is measured from the front of the library to the rear. In
Figure 20 on page 106, B refers to the distance (3044 mm or 119.8 in.) that is the total
service clearance between the front and the rear of the library.
3.
For libraries with service clearance on the right end only (as you face the front door),
visual access is also required on the left end as determined by the local service team.
This visual access allows the IBM Service Representative to see the 2-character display
on the left side of the cartridge accessor.
104
IBM System Storage TS3500 Tape Library with ALMS: Introduction and Planning Guide
Summary of Contents for System Storage TS3500
Page 1: ...IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide GA32 0593 07...
Page 6: ...vi IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 8: ...viii IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 14: ...xiv IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 18: ...xviii IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 24: ...xxiv IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 114: ...90 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 156: ...132 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 196: ...172 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 234: ...210 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 238: ...214 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 246: ...222 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 254: ...230 IBM System Storage TS3500 Tape Library with ALMS Introduction and Planning Guide...
Page 289: ......
Page 290: ...Printed in USA GA32 0593 07...