Installing the 2145 UPS-1U
Before you can use the SAN Volume Controller, you need to install the
uninterruptible power supply.
About this task
Complete the following steps to install the 2145 UPS-1U:
Procedure
1.
Install the support rails for the 2145 UPS-1U.
2.
Install the 2145 UPS-1U in the rack.
3.
Install the 2145 UPS-1U cable-retention bracket.
Installing the support rails for the 2145 UPS-1U
You must install the support rails in the rack before installing the 2145 UPS-1U.
Before you begin
Complete these prerequisites before installing the support rails:
1.
Use the customer's hardware-location chart to determine where in the rack to
install the 2145 UPS-1U.
2.
At the back of the rack, observe the Electronic Industries Alliance (EIA)
positions and determine where you are going to install the 2145 UPS-1U.
Because of its weight, position the 2145 UPS-1U where it is easy to handle in
one of the lower positions in the rack.
About this task
Perform the following steps to install the support rails for the 2145 UPS-1U:
Procedure
1.
Open the top of the 2145 UPS-1U shipping carton. Grip the flaps on either side
of the 2145 UPS-1U.
2.
Lift the 2145 UPS-1U clear of the shipping carton and place it on a flat, stable
surface with the front facing you.
3.
Attach the long side of a mounting bracket
1
to each side of the 2145 UPS-1U
using four M3
×
6 screws
2
for each bracket, as shown in Figure 8 on page
Chapter 2. Installing the SAN Volume Controller 2145-CG8 hardware
17
Summary of Contents for SAN Volume Controller 2145-CG8
Page 6: ...vi SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 8: ...viii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 28: ...xxviii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 34: ...6 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 72: ...44 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 100: ...72 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 102: ...74 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 104: ...76 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 109: ......
Page 110: ...Part Number 31P1669 Printed in USA GC27 3923 02 1P P N 31P1669...