EPO Connectors

J5

J6

J7

J8

J3

J2

Frame
Ground

Main Line

Customer
Power
Control

Figure

1-4. Primary Power Box (Rear View)

4. Place the transformer assembly according to “Service Clearances” on

page 1-2. The transformer must be installed above the raised floor (if present).

  IMPORTANT 

Ensure that the transformer is placed so that it will not cause a tripping
hazard. Place it against a wall, on or under a desk or table, away from
aisles.

5. Plug the output power cord of the transformer to connector J3. Secure the

cable with the clamp and screw removed in step 3a.

6. Route the input power cord to the customer's receptacle, and insert the power

plug into the customer's main socket.

7. Switch the transformer assembly circuit protector to the ON position.

8. Continue the 3745 installation using the

 Installation Guide Chapter 2, step 4 of

"3745 Connection to Customer's Primary Power".

 Operation

The transformer is a passive device requiring no action. The 3745 power
(ON/OFF) will still be controlled by the 3745 control panel. The circuit protector on
the transformer is for circuit protection only and should not be used as an ON/OFF
switch.

1-6

RPQ 7L1184 

 

Summary of Contents for RPQ 7L1184

Page 1: ...3745 Communication Controller Models 130 150 160 170 and 17A 3746 Expansion Unit Model 900 IBM 100 120 Volt Connection RPQ 7L1184 Installation and Maintenance Information SY33 2078 3...

Page 2: ......

Page 3: ...3745 Communication Controller Models 130 150 160 170 and 17A 3746 Expansion Unit Model 900 IBM 100 120 Volt Connection RPQ 7L1184 Installation and Maintenance Information SY33 2078 3...

Page 4: ...readers comments appears at the back of this publication If the form has been removed address your comments to International Business Machines Corporation Department 6R1LG 180 Kost Road Mechanicsburg...

Page 5: ...tion 1 1 Specifications 1 2 Dimensions 1 2 Service Clearances 1 2 Weight 1 2 Heat Output 1 2 Airflow 1 2 Power Requirements 1 2 Environment Operating 1 2 Plan View 1 3 Component Location 1 4 Installat...

Page 6: ...iv RPQ 7L1184...

Page 7: ...uant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment gener...

Page 8: ...vi RPQ 7L1184...

Page 9: ...assembly The areas checked by this procedure are 1 Input power voltage 2 Circuit protector 3 Safety label 4 Power supply part number 5 Grounding 6 Covers Important Note The transformer assembly is a...

Page 10: ...mer Assembly Part Number on page 1 8 Step 5 Grounding Check that electrical continuity is assured between the ground wires of the power cords and between those ground wires and the frame ground Step 6...

Page 11: ...Expansion Unit Model 900 to a customer s 100 120 volt power supply It consists of a transformer with an input power cord with a plug and an output power cord Overload protection is provided through a...

Page 12: ...37 25 lb Heat Output 50 W Airflow Convection only Power Requirements kVA 1 2 Phase 1 Input Current 11 A maximum for United States Canada 13 A maximum for Japan Inrush current 180 A maximum Branch circ...

Page 13: ...Plan View Metric scale 1 mm 5 mm Measurements in inches are shown in parentheses 1 A floor cutout is required for raised floor installation Figure 1 1 Plan View Chapter 1 Generalities 1 3...

Page 14: ...D e t a i l B N E P A S O U V R I R D O N O T O P E N 2 4 0 V D e t a i l B O u t p u t C o r d 2 I E C P l u g D O N O T O P E N S a f e t y l a b e l S e e D e t a i l C U S A a n d C A N A D A D e...

Page 15: ...nt of the 3745 primary power box see Figure 1 3 for location Voltage Selection Switch 220 200 240 J6 J7 J9 J8 F1 SW1 Main Line CB CB1 CP2 CP3 J1 Figure 1 3 Primary Power Box Front View On the front si...

Page 16: ...former to connector J3 Secure the cable with the clamp and screw removed in step 3a 6 Route the input power cord to the customer s receptacle and insert the power plug into the customer s main socket...

Page 17: ...nge check if the circuit protector is in the ON position For part number assembly refer to Transformer Assembly Part Number on page 1 8 AC Voltage Limits Input Voltages Voltages Canada Japan U S A Nom...

Page 18: ...F1232 7 46 3 57 18 14 U S A CANADA non locking plug 34F1233 4 46 3 57 18 14 U S A CANADA moisture resistant plug 34F1234 51 46 3 57 18 14 JAPAN locking plug 34F1235 2 1 3 2 72 51 1 6 JAPAN non locking...

Page 19: ...ormation Publication No SY33 2078 3 Please send us your comments concerning this book We will greatly appreciate them and will consider them for later releases of the present book If you prefer sendin...

Page 20: ...s We d Like to Hear from You SY33 2078 3 IBM Fold and Tape Please do not staple Fold and Tape PLACE POSTAGE STAMP HERE IBM France Centre d Etudes et Recherches Service 0798 BP 79 06610 La Gaude France...

Page 21: ......

Page 22: ...IBM Part Number 26F1485 Printed in U S A 26F1485 SY33 2 78 3...

Reviews: