© Copyright IBM Corp. 2003
15
Chapter 5. Rack PDU Specifications
When connected to a dedicated power source, the 100-127V and Universal Rack
PDUs conform to UL1950, CSA 22.2-950, EN-60950, and IEC-950 standards. The
following table contains the product specifications for the 100-127V and Universal
Rack PDUs.
Height
41.5 mm (1.63 in.)
Width
222.5 mm (8.76 in.)
Depth
114.5 mm (4.51 in.)
Additional Clearance
100-127V Rack PDU:
20 mm (0.79 in.) for circuit
breaker; 2.5 mm (0.1 in.) for outlets
Universal Rack PDU:
20 mm (0.79 in.) for circuit
breaker; 3.0 mm (0.12 in.) for outlets
Weight
100-127V Rack PDU:
1.7 kg (3.7 lb), with fixed line
cord
Universal Rack PDU:
1.3 kg (2.8 lb), without
power cord
Operating temperature at 0-914 m
(0-3000 ft)
10
°
-35
°
C (50
°
-95
°
F)
Operating temperature at 914-2133 m
(3000-7000 ft)
10
°
-32
°
C (50
°
-90
°
F)
Operating humidity
8-80% (non-condensing)
Rated voltage
100-127V Rack PDU:
100-127 V ac, 15 A, single-
phase
Universal Rack PDU:
100-240 V ac, 15 A, single-
phase
Rated frequency
50-60 Hz
Maximum power rating
100-127V Rack PDU:
1900 VA
Universal Rack PDU:
3600 VA
Circuit breaker
Two-pole, 15 A with time-delay protection
Power inlet
100-127V Rack PDU:
Fixed line cord with L5-15P
connector rated at 15 A
Universal Rack PDU:
IEC 320-C20 inlet rated at
16 A (VDE) / 20 A (UL/CSA)
Power outlets
100-127V Rack PDU:
Six NEMA 5-15 outlets rated
at 10 A (VDE) / 15 A (UL/CSA)
Universal Rack PDU:
Seven IEC 320-C13 outlets
rated at 10 A (VDE) / 15 A (UL/CSA)