EPUB_PRC_ALL_PROCS isolation procedure
A problem was detected with a system processor.
Use the following table to determine the service action:
Table 20. EPUB_PRC_ALL_PROCS service actions
System
Service action
8001-12C or 8005-12N
Replace the following items, one at a time, in the order
that is shown until the problem is resolved:
1.
System processor CPU 1
2.
System processor CPU 2
3.
System backplane
Go to “8001-12C or 8005-12N locations” on page 73 to
identify the physical location and removal and
replacement procedure. If the replacement of the system
processors and the system backplane does not resolve the
problem, go to “Contacting IBM service and support” on
page 71. This ends the procedure.
8001-22C or 8005-22N
Replace the following items, one at a time, in the order
that is shown until the problem is resolved:
1.
System processor CPU 1
2.
System processor CPU 2
3.
System backplane
Go to “8001-22C or 8005-22N locations” on page 87 to
identify the physical location and removal and
replacement procedure. If the replacement of the system
processors and the system backplane does not resolve the
problem, go to “Contacting IBM service and support” on
page 71. This ends the procedure.
EPUB_PRC_ALL_MEMCRDS isolation procedure
A problem was detected with a memory DIMM, but it cannot be isolated to a specific memory DIMM.
1.
Use the
ipmitool
command to examine system event logs (SELs).
v
To list SELs by using an in-band network, use the following command:
ipmitool sel elist
v
To list SELs remotely over the LAN, use the following command:
ipmitool -I lanplus -U <username> -P <password> -H <BMC IP addres or BMC hostname> sel elist
2.
Identify all SELs with the value
OEM record df
and Transition to Non-recoverable in the description.
Did you find one or more SELs with the value
OEM record df
and Transition to Non-recoverable in
the description?
If
Then
Yes:
Continue with the next step.
No:
Go to “Contacting IBM service and support” on page 71. This ends the procedure.
3.
For each of the SELs that you identified in step 2, determine the sensor name that is associated with
each SEL. Replace the following items, one at a time, until the problem is resolved:
62
Problem analysis, system parts, and locations for the 8001-12C, 8001-22C, 8005-12N, and 8005-22N
Summary of Contents for Power System 8001-12C
Page 2: ......
Page 102: ...86 Problem analysis system parts and locations for the 8001 12C 8001 22C 8005 12N and 8005 22N...
Page 111: ...System parts Figure 15 System parts Finding parts and locations 95...
Page 129: ......
Page 130: ...IBM...