INPUT REGISTRY
16-bit registry (Read).
Modbus function 04 "Read Input Registries" is used for reading.
Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Programme version
IOC
Latest version of the controller
card
UINT 16 Read
100
2
Programme version
MPC
Latest version of the base card
UINT 16 Read
100
3
VariMax model
Reads 100 for VariMax100 etc. UINT 16 Read
4
Temperature
Temperature in the control unit INT 16
Read
°C
5
AC voltage
Supply voltage for VariMax
UINT 16 Read
V
6
Operating mode
Source for speed reference
value(s) in current use:
1= Low speed DIP switch ON
2= High speed DIP switch ON
17 = Control signal
32 = INo operation. Blow-clean
function OFF
36 = Blow-clean function ON
44 = Blow-clean function
frequency 10 seconds
UINT 16 Read
7
Current reference
value for speed
(rpm)
UINT 16 Read
100
rpm
8
Current motor axle
speed
UINT 16 Read
100
rpm
9
Maximum motor
axle speed
Static value that advises the
max speed the control unit can
operate at.
UINT 16 Read
100
rpm
Continued on next page
23
Summary of Contents for VariMax100M
Page 2: ......
Page 14: ...12...
Page 15: ...13 M o d b u s...
Page 16: ...14...
Page 29: ...27 OWN NOTES...
Page 30: ...OWN NOTES 28...
Page 31: ...OWN NOTES 29...