INPUT REGISTRY
16-bit registry (Read).
Modbus function 04 "Read Input Registries" is used for reading.
Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Programme version
IOC
Latest version of the controller
card
UINT 16 Read
100
2
Programme version
MPC
Latest version of the base card
UINT 16 Read
100
3
VariMax model
Reads 100 for VariMax100 etc. UINT 16 Read
4
Temperature
Temperature in the control unit INT 16
Read
°C
5
AC voltage
Supply voltage for VariMax
UINT 16 Read
V
6
Operating mode
Source for speed reference
value(s) in current use:
1= Low speed DIP switch ON
2= High speed DIP switch ON
17 = Control signal
32 = INo operation. Blow-clean
function OFF
36 = Blow-clean function ON
44 = Blow-clean function
frequency 10 seconds
UINT 16 Read
7
Current reference
value for speed
(rpm)
UINT 16 Read
100
rpm
8
Current motor axle
speed
UINT 16 Read
100
rpm
9
Maximum motor
axle speed
Static value that advises the
max speed the control unit can
operate at.
UINT 16 Read
100
rpm
Continued on next page
23