INPUT REGISTER
16-bit register (Read).
Modbus function 04 "Read Input Registries" is used for reading.
Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Program version
IOC
UINT 16 Read
100
2
Program version
MPC
UINT 16 Read
100
3
VariMax model
Reads 50 for VariMax50 etc.
UINT 16 Read
4
Temperature
Temperature in the control unit INT 16
Read
°C
5
AC voltage
Supply voltage for VariMax
UINT 16 Read
V
6
Operating mode
Source for speed reference
value(s) in current use:
1 = Low speed DIP switch ON
2 = High speed DIP switch ON
3 = Manual speed
17 = Control signal
32 = No operation.
Cleaning function OFF
36 = No operation.
Cleaning function ON
44 = Cleaning function in
progress.
UINT 16 Read
7
Current reference
value for speed
(rpm)
UINT 16 Read
100
rpm
8
Current motor axle
speed
UINT 16 Read
100
rpm
9
Maximum motor
axle speed
Static value that advises the
max speed the control unit can
operate at.
UINT 16 Read
100
rpm
Continued on next page
22
Summary of Contents for F21050304
Page 2: ......
Page 14: ...12 ...
Page 15: ...13 M o d b u s ...
Page 16: ...14 ...
Page 29: ...27 PERSONAL NOTES ...
Page 30: ...28 PERSONAL NOTES ...
Page 31: ...29 PERSONAL NOTES ...