Figure 22
Allowed SST installation orientations
The SST vent/air connections fit Sched. 40 three inch PVC/CPVC pipe. PP pipe cannot be
used with the SST. The pipes must extend completely through the wall as shown below,
and immediately inside the wall, adapt up to a 4 inch pipe using a standard reducing
coupling fitting. Do not use a bushing. The SST is an external fixture, and is not part of the
sealed vent system that runs inside the building.
Figure 23
Pipes extend completely through the wall (Vertical orientation shown)
Ensure that the vent termination location does not exceed the allowed maximum
equivalent vent length, including the allowance for the SST.
Install multiple vent SST installations level with one another and maintain at least the
minimum separation distances shown below. The terminals shall not be stacked vertically.
Figure 24 :
Minimum separation for multiple
vent installation - vertical orientation
Figure 25 :
Minimum separations for multiple vent
installation - horizontal orientation
Approved PVC Side Wall Termination kits are listed below:
Ipex # 196985 3" (SL 26-260 G3)
Ipex # 196986 4" (SL 40-399 G3)
Figure 26
Approved PVC Side Wall Termination configuration
35
3.7.6 Sidewall vent termination
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...