Miscellaneous errors
Issue
Diagnosis
Fix
Error - Max. Inlet/Outlet Sensor Temp.
Exceeded. > Check water flow Water
temperature signal not within acceptable range.
Potential flow or sensor failure. Consult service
technician.
Current outlet
temperature
exceeds
operating limit.
Check water flow.
Defective or
disconnected
temperature
sensor.
Check wiring to
temperature sensor and
control module.
Check temperature
sensor.
Blank – screen dark, but fan running Indicative of
power-surge damage to appliance
Check transformer;
replace if damaged.
Check circuit board for
visible damage.
Controller is stuck in "service" mode after
software update.
If update fails
or no updates
applied.
Restarting returns the
boiler to normal
operation.
8.3.1 Ignition issues
Ignition issues
Issue
Diagnosis
Fix
Noisy spark when igniting
Ignition lead is not firmly
connected.
Reconnect ignition lead.
Contaminants/moisture
on ignitor probe/flame
sensor.
Ensure probe is dry by re-running
post-purge; otherwise, clean or
replace ignitor probe.
Boiler rumbles when igniting.
Fluctuating gas
pressure/ gas pressure
too high/too low.
Check CO
2
level via analyzer.
Check for proper gas
piping
Check pressure with manometer
during ignition.
Boiler will not attempt to ignite.
Fan and pump are operating
normally.
No power to ignition
control module.
Check system wiring.
Check air reference tubing.
99
8.3.1 Ignition issues
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...